Please adhere to the actual products in case of any discrepancies in this user manual.
If you encounter any problem on the inverter, please find out the inverter S/N
and contact us, we will try to respond to your question ASAP.
Solis S5
Single
Phase Inverter
Installation and Operation Manual
S5-GR1P(7-10)K
Ginlong Technologies Co., Ltd.
Ver1.1

Advertisement

Table of Contents
loading

Summary of Contents for SOLIS S5

  • Page 1 Solis S5 Single Phase Inverter Installation and Operation Manual S5-GR1P(7-10)K Ver1.1 Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806 Fax: +86 (0)574 6578 1606 Please adhere to the actual products in case of any discrepancies in this user manual.
  • Page 2: Table Of Contents

    Contents 1. Introduction …………………………………………………………………………………………………………………………… 1.1 Product Description ………………………………………………………………………………………………………… 1.2 Packaging ………………………………………………………………………………………………………………………… 1.3 Product Storage ………………………………………………………………………………………………………………………… 2. Safety Instructions …………………………………………………………………………………………………………… 2.1 Safety Symbols ………………………………………………………………………………………………………………… 2.2 General Safety Instructions …………………………………………………………………………………………… 2.3 Notice For Use ………………………………………………………………………………………………………………… 2.4 Notice for Disposal ……………………………………………………………………………………………………………… 3. Overview ………………………………………………………………………………………………………………………………...
  • Page 3: Introduction

    1. Introduction 1.1 Product Description 1.2 Packaging Solis S5 Single Phase Inverters integrate DRM and backflow power control function, that When you receive the inverter, please ensure that all the parts listed below are included: could suitable for smart grid requirement.
  • Page 4: Product Storage

    1. Introduction 2. Safety Instructions 1.3 Product Storage 2.1 Safety Symbols If the inverter is not to be installed immediately, storage instructions and environmental Safety symbols used in this manual, which highlight potential safety risks and important conditions are below: safety information, are listed as follows: Use the original box to repackage the inverter, seal with adhesive tape with the desiccant inside the box.
  • Page 5: Notice For Use

    The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC Article 690, Part II. All Solis S6 Single Phase Inverters feature an integrated DC switch. CAUTION: The PV array (Solar panels) supplies a DC voltage when they are exposed to sunlight.
  • Page 6: Overview

    3. Overview 4. Installation 3.1 Front Panel Display 4.1 Select a Location for the Inverter To select a location for the inverter, the following criteria should be considered: WARNING: Risk of fire Despite careful construction, electrical devices can cause fires. Do not install the inverter in areas containing highly flammable materials or gases.
  • Page 7: Mounting The Inverter

    4. Installation 4. Installation 4.2 Mounting the Inverter Install on a wall or strong structure capable of bearing the weight. Dimensions of mounting bracket: Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
  • Page 8: Electrical Connections

    3. Assemble PV input connector to the Inverter. Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter. Maximum 600Vdc for S5-GR1P7K, S5-GR1P8K, S5-GR1P9K, S5-GR1P10K Before connection, please make sure the polarity of the output voltage of PV array matches the“DC+”and“DC-”symbols.
  • Page 9 4. Installation 4. Installation Crimping plier Figure 4.12 Crimp the contact pin to the wire Figure 4.13 Connector with Cap nut Screwed on Figure 4.8 DC+ Connector Figure 4.9 DC- Connector Please use approved DC cable for PV system. Figure 4.14 Connect the DC Connectors to the Inverter Cross section(mm²)...
  • Page 10 4. Installation 4. Installation 4.3.2 AC output connections It is recommended to use 6-16mm2 outdoor cables with a crimp terminal range of 6-10mm2. 3. Dissemble the 4 screws on the AC terminal cover and take out the cover. Installation steps are shown as below: 1.
  • Page 11 45.5/43.5 Table 4.3 Rating of grid OCPD 4.3.5 Inverter monitoring connection The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are optional (Figure 4.21). For connection instructions, please refer to the Solis Monitoring Device installation manuals.
  • Page 12 External CT Type Meter - 120A/40mA CT is supplied (Model: ACR10RD16TE) N PE Customer can place the order for a suitable meter from Solis Sales Reps. Figure 4.24 Direct Insert Type Meter - “Meter in Load” Below are the connection diagrams of different meters connecting to different locations.
  • Page 13 Meter Model can only connect a smart meter. RJ45 Connector CT Model can only connect a smart sensor. 5 6 7 8 9 10 21 22 23 Please consult Solis Sales Rep before placing the order. White Black Load 2-Pin Connector...
  • Page 14: Start & Stop

    1. Select "Grid Off" in the Advanced Setting of Inverter LCD. 1--8 Rj45 plug 2. Turn off the AC Switch between Solis inverter and Grid. Correspondence between the cable s Rj45terminal and the stitch es of plug, Pin5 and Pin6 3.
  • Page 15: Operation

    NULL 10 sec DRM Number: The Solis S6 Single Phase Inverter main menu provides access to operational data and DRM Number: Show the number 01-08. information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.
  • Page 16: Settings

    This function is used to set the address when muti inverters are connected to single monitor. The address number can be assigned from “01”to “99”. Alarm001: OV-G-V The default address number of Solis S6 Single Phase Inverter is “01”. Time: 00-00 Data: 7171 YES=<ENT>...
  • Page 17 6. Operation 6. Operation 6.4.3 Version 6.4.6 Yearly Energy The screen shows the model version and the software version of the Inverter The function is for checking the energy generation for selected year. Model: 08 YES=<ENT> NO=<ESC> Software Version: D20001 Select: 2020 Figure 6.7 Model Version and Software Version...
  • Page 18: Advanced Settings

    6.5.2 Grid ON/OFF Press the UP/DOWN keys to select the standard (AS4777-02,AS4777-15, VDE4105, VDE0126, This function is used to start up or stop the power generation of Solis Single Phase Inverter. UL-240V-A, UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3 (for 4-5kW models), C10/11, EN50438 DK, EN50438 IE, EN50438 NL and “User-Def”...
  • Page 19 Until the sunrise, the system will start to work again while the meter data can be uploaded to the Solis monitoring system 6.5.7 Calibrate Energy to calibrate the load consumption data.
  • Page 20 HMI will for the whole day and the data will be displayed on the Solis monitoring system. display “Limit by DRM” and the inverter output power will be limited to zero.
  • Page 21 (If necessary). -> CT Sampling Ratio YES=<ENT> NO=<ESC> Ratio:3000:1 Step 7: Configure the Solis monitoring system (Please refer to the manual of monitoring device) ·CT Link Test If customer does not want to enable the export power control function, please This setting is used to check the direction of the CT (Not complusory) change the "backflow power"...
  • Page 22 Negative values indicate a more strict control to limit the export power in This setting should only be turned on when Solis external EPM device is used. advance thus ensuring exact no power is feeding into the grid. Two options are available:5G-EPM and Others-EPM.
  • Page 23: Afci Function

    ARC-FAULT 6.6 AFCI function Restart Press ESC 3s Solis inverters have the built-in AFCI function which can detect the arc fault on the DC circuit Figure 6.29 Arc Fault and shut down the inverter to prevent a fire disaster. Installer needs to thoroughly inspect the DC circuit to ensure all the cables are 6.6.1 Enable the AFCI function...
  • Page 24: Maintenance

    7. Maintenance 8. Troubleshooting Solis S6 Single Phase Inverter does not require any regular maintenance. Alarm Message Failure description Solution However, cleaning the dust on heat-sink will help the inverter to dissipate the heat and 1.Check PV input connections increase its life time. The dust can be removed with a soft brush.
  • Page 25: Specifications

    1. Serial number of Solis Single Phase Inverter; RD 1699 / RD 244 / UNE 206006 / UNE 206007-1, Grid connection standard 2. The distributor/dealer of Solis Single Phase Inverter (if available); CEI 0-21, C10/11, NRS 097-2-1,EIFS 2018.2, IEC 62116, IEC 61727, IEC60068, IEC 61683, 3.
  • Page 26 9. Specifications 9. Specifications Model S5-GR1P8K Model S5-GR1P9K Max. DC input voltage (Volts) Max. DC input voltage (Volts) Rated DC voltage (Volts) Rated DC voltage (Volts) Startup voltage (Volts) Startup voltage (Volts) MPPT voltage range (Volts) MPPT voltage range (Volts)
  • Page 27: Appendix

    It is for your reference only. If customer has any doubts or uncertainty, please Rated output current (Amps) 45.5/43.5 consult Solis service department for confirmation. Max. output current (Amps) 45.9 To set the correct grid code, please enter the following path: >0.99 (0.8 leading - 0.8 lagging)
  • Page 28 10. Appendix Code in LCD Country/Region Comments G98 NI North Ireland For North Ireland Low Voltage Grid <16A G99 NI North Ireland For North Ireland Low Voltage Grid >16A User-define Customized Protection Limits Gen50 Generator Connected, Frequency-Derating, 50Hz Gen 60 Generator Connected, Frequency-Derating, 60Hz East Denmark For East Danish low voltage grid...