If you encounter any problem on the inverter, please find out the inverter S/N
and contact us, we will try to respond to your question ASAP.
UK mark for conformity
Solis S5-EH1P-L Hybrid Inverter
Instruction Manual
Ginlong Technologies Co., Ltd.
Ver1.1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the S5-EH1P-L and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SOLIS S5-EH1P-L

  • Page 1 Solis S5-EH1P-L Hybrid Inverter Instruction Manual Ver1.1 Ginlong Technologies Co., Ltd. No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China. Tel: +86 (0)574 6578 1806 Fax: +86 (0)574 6578 1606 Please adhere to the actual products in case of any discrepancies in this user manual.
  • Page 2: Table Of Contents

    Contents 1. Introduction ……………………………………………………………………………………………………………………………… 1.1 Product Description ……………………………………………………………………………………………………………… 1.2 Packaging ………………………………………………………………………………………………………………………………… 2. Safety & Warning ……………………………………………………………………………………………………………… 2.1 Safety ………………………………………………………………………………………………………………………………………… 2.2 General Safety Instructions ………………………………………………………………………………………………… 2.3 Notice For Use ………………………………………………………………………………………………………………………… 3. Overview …………………………………………………………………………………………………………………………………… 3.1 Screen ………………………………………………………………………………………………………………………………………… 3.2 Keypad ……………………………………………………………………………………………………………………………………… 3.3 Terminal Connection ………………………………………………………………………………………………………………...
  • Page 3: Introduction

    1.2 Packaging 1.1 Product Description The Solis S5-EH1P-L Series is designed for residential hybrid systems, which can work Please ensure that the following items are included in the packaging with your machine: with batteries to optimize self-consumption. The unit can operate in both off-grid and on-grid modes.
  • Page 4: Safety & Warning

    Electrical installations must be done in accordance with the local and national electrical safety standards. WARNING: AC BACKUP Port of S5-EH1P-L Series is not allowed to connect to the grid. WARNING: Do not touch any inner live parts until 5 minutes after disconnection from the utility grid and the PV input.
  • Page 5: Notice For Use

    2. Safety & Warning 3. Overview 3.1 Screen Solis S5-EH1P-L Series adopts 7 inch color screen, it displays the status, operating information and settings of the inverter. WARNING: The S5-EH1P-L Series does not support parallel (three- and single-phase) 3.2 Keypad operation on the AC-BACKUP port.
  • Page 6: Installation

    4. Installation 4. Installation 4.1 Select a Location for the Inverter Install on a wall or strong structure capable of bearing the weight of the machine (18.3kg). To select a location for the inverter, the following criteria should be considered: Install vertically with a maximum incline of +/- 5 degrees, exceeding this may cause Exposure to direct sunlight may cause output power derating.
  • Page 7: Mounting The Inverter

    4. Installation 4. Installation 4.2 Mounting the Inverter Dimensions of mounting bracket: Suitable fixing screws Φ6.8 Bracket 11.8 Locking screw Figure 4.4 Fix bracket on the wall WARNING: The inverter must be mounted vertically. 2. Lift up the inverter (be careful to avoid injury), and align the back bracket on the inverter with the convex section of the mounting bracket.
  • Page 8: Pe Cable Installation

    4. Installation 4. Installation 4.3 PE Cable Installation 4.4 PV Input Cable Installation An external ground connection is provided at the right side of inverter. Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal. Before connecting inverter, please make sure the PV array open circuit Connect the OT terminal with ground cable to the right side of inverter.
  • Page 9 4. Installation 4. Installation 3. Pass the stripped DC cable through the nut and waterproof rubber ring. 6. Measure PV voltage of DC input with multimeter, verify DC input cable polarity. Positive terminal Negative terminal Figure 4.9 Figure 4.12 4. Connect the wire part of the DC cable to the metal DC terminal and crimp it with a special DC terminal crimping tool.
  • Page 10: Battery Power Cable Installation

    4. Installation 4. Installation 4.5 Battery Power Cable Installation 4.5.1 Normal battery cable installation 4.5.2 Extended battery cable installation If the battery cable size is required to be changed by the battery manufactuer, please refer to following content for the cable preparation. Otherwise, you may skip these steps. NOTE: External battery switch must be installed between the battery and inverter for safe maintenance purpose if the battery does not have built-in DC breaker.
  • Page 11 4. Installation 4. Installation Step 2: Un-assemble Grommet and Back shell over the cable as shown. Step 4: Crimping the lug as shown. Crimping heigth is 7.5+0/-0.2mm Grommet Back shell Gap is 1.0 mm Ref. ± Crimping length is 7.5 0.5 Correct direction: The chamfer in the rear position Figure 4.20 Wrong direction: The chamfer at the front position...
  • Page 12: Ac Cable Installation

    4. Installation 4. Installation 4.6 AC Cable Installation Step 5: Install grommet and back shel. There are two AC terminals and the assembly steps for both are the same. TakeouttheACconnectorpartsfromthepackaging. Assemble the grommet onto the connector body firstly Describe Numerical value Cable diameter 10~14mm Traverse cross sectional area...
  • Page 13: Communication Cable Installation

    1. (Optional) To realize Demand Response or Logic DRM Port interface function, this function may be required in UK and Australia. 1. (Optional) Used for Solis Data Logger Connection. 2. (Optional) Used for Modbus RTU communication with COM Port a 3rd party external device.
  • Page 14 If lead-acid battery is used and battery temperature sensor is needed, Figure 4.31 please contact your distributor or Solis sales to purchase individually. 1. Insert the RJ45 terminal end to the CAN port at the bottom of the inverter and fasten the swivel nut.
  • Page 15 Figure 4.35 A RJ45 terminal is used for DRM connection. 3. Rotate the black ring on the Solis Data Logger in clockwise to secure the connection. Assignment for inverters capable Assignment for inverters capable of both charging and discharging...
  • Page 16: Meter Installation

    Smart Meter. 2. One Smart Meter can be used with only one hybrid inverter. The Solis S5-EH1P-L Series inverter is able to connected Acrel meters or Eastron meters to fuilfill the control logic of the self-consumption mode, export power control, monitoring, etc.
  • Page 17 4. Installation 4. Installation 4.8.1 Single phase meter installation .29. .30.
  • Page 18 4. Installation 4. Installation 4.8.2 Three phase meter installation .31. .32.
  • Page 19: Led Indicators

    4. Installation 5. Commissioning 4.9 LED Indicators 5.1 Preparation of Commissioning Ensure all the devices are accessible for operation, maintenance and service. There are three LED indicators on the RHI inverter (Red, Green, and Orange) which indicate the working status of the inverter. Check and confirm that the inverter is firmly installed.
  • Page 20 5. Commissioning 5. Commissioning 4. Enter advanced settings (do not repeat this step for all subsequent operations). 5. Select the local grid standard code. Menu Settings Advanced Settings Settings Select Standard 2015-02-23 19 35 2015-02-23 19 35 2015-02-23 19 35 Information Export Power Set Select Standard...
  • Page 21 5. Commissioning 5. Commissioning 6. Check the backup supply settings. If you don't have a backup circuit on the backup port, 7. Select the battery option and set battery SOC disable it. Otherwise, keep it as enable and refer to section 4.6 for the installation process The default setting for overdischarge SOC is 20%, force charging SOC is 10%, force of AC backup connector.
  • Page 22 5. Commissioning 5. Commissioning 8. Select the storage work mode. Recommended settings - Self-Use Mode. This mode can maximize the use of Brand Model Setting photovoltaic power generation directly for household electricity, or store it in batteries Box Pro 2.5-13.8 Select "B-BOX"...
  • Page 23 5. Commissioning 5. Commissioning 8. Please check in the accessory package and confirm the meter type first. 9. Switch on the inverter DC switch. 10. Switch on battery breaker. If the default meter is Acrel ACR10R16DTE, please select the meter type as "1PH Meter". If the default meter is Eastron SDM120CT, please select the meter type as "Eastron 1PH 11.
  • Page 24: Shutdown Procedure

    5. Commissioning 6. Operation 5.3 Shutdown procedure 1. Turn off the AC isolator at the grid connection point. 2. Turn off the DC switch of the inverter. Pressing the ESC main menu 3. Turn off the DC switch between inverter and battery. key calls back the previous menu 4.
  • Page 25: Main Menu

    6. Operation 6. Operation 6.2 Main Menu After setting the language, press "ESC" to access the main page. There are four submenu in the Main Menu: 1. Information 2. Settings 3. Advanced Information 4. Advanced Settings 0.00kW 2.526 Menu Settings 0.00kW 2015-02-23 19 35 0.00kW...
  • Page 26 Information for "PV Inverter Meter" is only available when two Eastron BMS Status: Normal meters are used and Meter Placement is selected as "Grid+PV Meter". 3 / 4 Details please consult Solis service department. E S C D O W N E N T Figure 6.7 Information Page 3 .47.
  • Page 27: Settings

    Set the time and date on the inverter. Must set this according to local time as it Set system language. Chinese and English are available. affects the daily yield calculation. (If Solis monitoring system is used, must set Settings Set Language...
  • Page 28: Advanced Info

    6. Operation 6. Operation 6.5 Advanced Information 6.5.2 Running Message Detailed information can be viewed in this section: This function is for maintenance person to get running message such as internal 1.Alarm Message temperature, Standard NO. etc.(Values are for reference only). 2.Running Message Settings Running Message...
  • Page 29 6. Operation 6. Operation 6.5.4 Communication Data 6.5.6 Monthly Energy Internal communication data can be viewed in this section. For maintenance person only. The screen shows the inverter monthly energy detail of different month. Values are for reference only. Settings Monthly Energy 2015-02-23 19 35 Communication Data...
  • Page 30: Advanced Settings - Technicians Only

    6. Operation 6. Operation 6.5.8 Total Energy 6.6 Advanced Settings - Technicians Only The screen shows the inverter total energy detail. NOTE: Settings Total Energy This function is for authorised technicians only. Improper access 2015-02-23 19 35 and operation may result in abnormal results and damage to the inverter. 3 .
  • Page 31 This following list illustrates the grid standard options in the inverter which are subject to change. It is for your reference only. If customer has any doubts or uncertainty, please consult Solis service department for confirmation. Detailed protection limits can be viewed when choosing the code.
  • Page 32 6. Operation 6. Operation 6.6.3 Calibrate Warranty or maintenance may result in resetting total generating data, this function allow PowerParameter the maintenance personnel to amend the total generating data of replacement inverter to Adjusting total generating power Power Para: 1.000 the original one.
  • Page 33 Settings Storage Energy Set 2015-02-23 19 35 in the scope of inverter warranty or compensation. Please refer to the battery compatible list on Solis company website for Control Parameter information on latest compatible battery models. Battery Select For above compatible battery modules, Only three parameters need to be defined:...
  • Page 34 6. Operation 6. Operation Settings Battery Select 2015-02-23 19 35 NOTE: 5G products support lead-acid battery. Select "Lead-Acid" in the "Battery Select" and configure the following parameters according OverDischg SOC: 020% to different lead-acid batteries. Settings Lead Acid Battery 2015-02-23 19 35 Battery Capacity: 100Ah Equalizing Voltage:...
  • Page 35 Due to the inconformity between battery cells, damages will be less likely 1Ph Meter to be avoided. Solis is not responsible for any potential damages caused by the use of lead-acid batteries. Y E S = < E N T > N O = < E S C >...
  • Page 36 6. Operation 6. Operation 6.6.6.3.2 Meter Placement Mode 1: Self-Use Mode Logic(Maximize the usage of PV) PV Power Using Priority: Load>Battery>Grid Grid: Meter is installed at the grid connection point. Load Support Priority: PV>Battery>Grid Load: Meter is installed at the load branch circuit. Battery Charging Power comes from PV.
  • Page 37 6. Operation 6. Operation Mode 2: Feed In Priority Mode Logic(Feed the excess PV to Grid in order to gain Mode 3: Backup Mode Logic(Keep the Battery at a certain SOC and only use it subsidies) during power outage) PV Power Using Priority: Load>Grid>Battery Backup Mode Logic: Keep the Battery at a certain SOC and only use it during power Load Support Priority: PV>Battery>Grid outage.
  • Page 38 6. Operation 6. Operation Mode 4: Off-Grid Mode Logic(For Off-grid use and AC-Grid Port Disconnected) 6.6.7 Export power Set OverDischg SOC for Off-Grid Setting Range: From Battery “Forcecharge SOC” to 100% This function is to set the export power control. PV Power Using Priority: Load>Battery 1.Backflow Power.
  • Page 39 6. Operation 6. Operation 6.6.7.2 ON/OFF 6.6.8 HMI Update Enable/Disable the function. This function is used to update HMI software. Values are for reference only. Settings ON/OFF 2015-02-23 19 35 HMIUpdate 2015-02-23 19 35 The Current Version:F0 Y E S = < E N T > N O = < E S C > C A N C E = <...
  • Page 40 6. Operation 6. Operation 6.6.10 BaudRate RS485 6.6.11.1 AFCI Set Inverters have the built-in AFCI function which can detect the arc fault on the This function is to change the internal communication Baudrate. DC circuit and shut down the inverter to prevent a fire disaster. Settings BaudRate RS485 2015-02-23 19 35...
  • Page 41 6.6.11.2 EPS Mode During the normal operation, if an DC arc is detected, the inverter will shut down and EPS Mode needs to work with external Solis NPS switching box to achieve ATS give out the following alarm: switching function.
  • Page 42: Maintenance

    7. Maintenance 8. Troubleshooting Solis S5-EH1P-L Series inverter does not require any regular maintenance. However, cleaning the The inverter has been designed in accordance with international grid tied standards for heatsink will help inverter dissipating heat and increase the lifetime of inverter. The dirt on the safety, and electromagnetic compatibility requirements.
  • Page 43 8. Troubleshooting 8. Troubleshooting Message Name Information Description Troubleshooting Suggestion Message Name Information Description Troubleshooting Suggestion 1. Turn on the device in the ON/OFF Setting. Control device to shutdown 1. Grid side fault, restart the device. Surge Alarm On-site grid surge If it is still not eliminated, please contact the 1.
  • Page 44 8. Troubleshooting 8. Troubleshooting Message Name Information Description Troubleshooting Suggestion Message Name Information Description Troubleshooting Suggestion 1. Confirm whether the battery model selection 1. Confirm that the grid is abnormal. Wrong battery brand selection BatName-FAIL is consistent with the actual one. 2.
  • Page 45: Specifications

    Rated output power 1. Serial number of Solis Single Phase Inverter; Max. apparent output power 4.5 kVA, 10SEC 2. The distributor/dealer of Solis Single Phase Inverter (if available); 3. Installation date. Back-up switch time <20ms 4. The description of problem (i.e. the alarm message displayed on the LCD and the status...
  • Page 46 9. Specifications 9. Specifications Technical Data S5-EH1P3K-L S5-EH1P3.6K-L Technical Data S5-EH1P3K-L S5-EH1P3.6K-L Output AC(Grid side) General data Rated output power Dimensions(W/H/D) 3.6kW 333*505*249mm Max. apparent output power Weight 18.3kg 3.3kVA 4kVA Operation phase 1/N/PE Topology High frequency insolation (for battery) Rated grid voltage Operation temperature range 220 V/230 V...
  • Page 47 9. Specifications 9. Specifications Technical Data S5-EH1P4.6K-L S5-EH1P5K-L* Technical Data S5-EH1P4.6K-L S5-EH1P5K-L* Input DC (PV side) Output AC(Grid side) Recommended max. PV power Rated output power 8000W 8000W 4.6kW Max. input voltage Max. apparent output power 600V 4.6kVA 5.5kVA* Rated voltage 330V Operation phase 1/N/PE...
  • Page 48 9. Specifications 9. Specifications Technical Data S5-EH1P4.6K-L S5-EH1P5K-L* Technical Data S5-EH1P6K-L* Input DC (PV side) General data Dimensions(W/H/D) Recommended max. PV power 333*505*249mm 8000W Weight 18.3kg Max. input voltage 600V Topology High frequency insolation (for battery) Rated voltage 330V Operation temperature range Start-up voltage -25℃~+60℃...
  • Page 49 9. Specifications 9. Specifications Technical Data S5-EH1P6K-L* Technical Data S5-EH1P6K-L* Output AC(Grid side) General data Rated output power Dimensions(W/H/D) 333*505*249mm Max. apparent output power Weight 18.3kg 6.6kVA Operation phase 1/N/PE Topology High frequency insolation (for battery) Rated grid voltage Operation temperature range 220 V/230 V -25℃~+60℃...