PRESTART CHECKLIST

Before starting the unit, all items in the prestart checklist must be completed. This checklist applies to both manual
and remote starting of the unit.
 Read and understand ALL safety sections at the beginning of this manual.
 Ensure all maintenance procedures are up to date. For more information, refer to
Maintenance" on page 38
 The unit must be level.
 The unit must be dry. Check for any water inside, on, or near the unit; dry if needed.
 Ensure the unit is properly grounded to a good earthen ground. Installation should be in compliance
with the National Electrical Code (NEC), state and local regulations.
 Switch the Control Power switch to the OFF (O) position.
 Switch all circuit breakers to the OFF (O) position.
 Inspect all electrical cords; repair or replace any that are cut, worn, or bare.
 Ensure all winch cables are in good condition and centered on each pulley. Do not use if cables are
kinked or beginning to unravel.
 Check oil, coolant, and fuel levels. For more information, refer to
 Ensure battery connections are secure.
 Turn the battery disconnect switch on, if equipped.
 Check the engine fan belt tension and condition.
26
120/208V 3-PHASE
120/240V 3-PHASE
4 Position Voltage Selector Switch Option
120/240V 1-PHASE
and
"Basic Maintenance Schedule - Isuzu Engine" on page
L1-L2 = 208V
L1-N = 120V
L2-L3 = 208V
L2-N = 120V
L3-L1 = 208V
L3-N = 120V
VOLTAGES AT RECEPTACLES
RECEPTACLE
GFCI
GFCI w/Buck
Twist-locks
L1-L2 = 240V
L1-N = 120V
L2-L3 = 240V
L2-N = 208V
L3-L1 = 240V
L3-N = 120V
VOLTAGES AT RECEPTACLES
RECEPTACLE
GFCI
GFCI w/Buck
Twist-locks
L1-L2 =
-
L1-N = 120V
L2-L3 =
-
L2-N =
L3-L1 = 240V
L3-N = 120V
VOLTAGES AT RECEPTACLES
RECEPTACLE
GFCI
GFCI w/Buck
Twist-locks
"General Maintenance" on page
N =
L-L
L-N
-
120V
-
120V
208V
120V
00085
N =
L-L
L-N
-
120V
-
120V
120V
0/120V
00086
N =
-
L-L
L-N
-
120V
-
120V
240V
120V
00087