5.2. ELECTRICAL CONNECTION - GENERAL
IMPORTANT!
The electrical connection of the unit must be carried out by qualified personnel, in compliance with
the regulations applicable in the country where the unit is installed. Non-conforming electrical con-
nections releases Jaga N.V. from liability concerning damage to objects and persons.
DANGER!
–  Always install a general automatic switch in a protected area near the unit, which has a characteris-
tic delayed curve, sufficient capacity and breaking power. There must be a minimum distance of 3
mm between the contacts.
–  Earth connection is compulsory by law to ensure user safety while the unit is in use.
–  Check that the voltage and the frequency of the electrical system correspond to 120V (±10%) single
phase at 60Hz; that the available installed power is sufficient for running the equipment and that
the supply cables are of adequate section for the maximum current required.
–  Make sure the electrical supply system complies with current National safety regulations.
–  The connections must be implemented in accordance with the diagrams supplied with the unit.
Use an H05RN-F type, flexible, double insulated, bipolar + earth cable with a 1.5 mm² section to
connect the unit to the mains.
–  If the unit is mounted on a metal surface, the earth connection must be installed in compliance with
local regulations. The earth conductor must be longer than the other conductors so that it is the last
one to release in the event the connection comes loose.
6
NEUTRAL (N)
L (HOT)
CIRCUIT BREAKER OR FUSE
MAX. 15 AMPS
To be provided by the installer. The circuit breaker
or fuse need to provide full disconnection from the
supply mains in all poles under overvoltage category III
accordance with the wiring rules.
JAGA CANADA | BRIZA 26 | MANUEL | 2022.09.27 | V.01
Blower
Motor
N
L
GND
Speed control input
As reference: controlled by external
thermostat (not included)
0-10V

Advertisement