5. GENERAL INFORMATION
DANGER!
The unit is not intended for industrial applications.
Do not insert objects into the supply and return air openings.
IMPORTANT!
–  the unit will only function correctly if the installation and operation manual is strictly followed.
–  all clearances indicated in the manual must be respected in order to guarantee performance, and to
allow installation and maintenance.
–  in case valve packages are to be installed, make sure that there is enough room left.
–  periodic access to the unit is required for inspection, maintenance and repairs.
–  pay attention to the signs and symbols indicated on the fan coil units.
Unit identification:
The serial number is tagged on unit's right side (on the left if the connections are on the unit's right
side).
Information regarding unintended use:
EN
The unit has been designed to function as a fan coil for both heating and cooling applications; any
other use is strictly forbidden. Installing the unit in an explosive environment is prohibited.
Decommissioning:
When the unit is not used for long periods of time, it must be disconnected from the mains electrical
connection.
If the unit is not used during the winter period, the water in the system may freeze. A suitable quantity
of anti-freeze liquid should be mixed with the water.
Mixing the water with glycol modifies the unit's performance. Pay attention to the safety
instructions on the packaging regarding glycol.
Restart after prolonged shutdown:
Before restarting:
–  clean or replace the stainless steel fan guard.
–  clean the coil.
–  clean or unclog the condensate drain.
–  bleed the air from the hydronic system.
–  it is advisable to run the unit at maximum speed and to check for abnormalities.
5.1. OPERATIONAL LIMITS:
An installation that does not meet the specified operational limits releases Jaga NV from all liability
with respect to damage to objects or people.
–  mains voltage: 120V - 1 ph - 60Hz
–  maximum water inlet temperature: 90°C - 194°F
–  maximum exchanger pressure: 20 bar - 290PSI
–  supply voltage: 120V ±10 %
JAGA CANADA | BRIZA 26 | MANUEL | 2022.09.27 | V.01