...6 CONFIGURATION – ADVANCED LEVEL
...6.2.4 Mass Flow 1 and 2
MATHS M
INPUT a
SOURCE
ANLG I/P
MATHS M
M
TEMPERATURE INPUT
SOURCE
ANLG I/P
MATHS M
NONE
None
M
TEMPERATURE UNITS
ABSOLUTE K or R
M
REFERENCE Tr
M
REFERENCE Tr
DECPT
M
PRESSURE INPUT
SOURCE
ANLG I/P
MATHS M
NONE
None
M
REFERENCE Pr
M
REFERENCE Pr
DECPT
M
SCALING CONSTANT
M
SCALING CONSTANT
DECPT
BLOCK TO CONFIGURE
M
64
Input Source
Select the input source required for input a. The source is selected from analog
inputs A1 to A6, B1 to B6 (depending on the options fitted – see Section 4.2) or
math functions M1 to M4.
Temperature Input Source
Select the input source required for the temperature input. The source is selected
from analog inputs A1 to A6, B1 to B6 (depending on the options fitted – see
Section 4.2) or math functions M1 to M4.
Temperature Units
Select the input source temperature units:
Deg F
Deg F
Deg C
Deg C
ABSOLUTE K or R – Input source measured in degrees absolute
Reference Temperature
Set the value which represents the reference temperature, between 0 and +9999.
The decimal point is set in the next parameter.
Reference Temperature Decimal Point
Set the number of decimal places required for the reference temperature (0 to 3
places).
Pressure Input Source
Select the input source required for the absolute pressure input. The source is
selected from analog inputs A1 to A6, B1 to B6 (depending on the options fitted
– see Section 4.2) or math functions M1 to M4.
Reference Pressure
Set the value which represents the absolute reference pressure to between 0 and
+9999. The decimal point is set in the next parameter.
Reference Pressure Decimal Point
Set the number of decimal places required for the absolute reference pressure (0
to 3 places).
Scaling Constant
Set the value which represents the scaling constant (k), between 0 and +9999.
The decimal point is set in the next parameter.
Scaling Constant Decimal Point
Set the number of decimal places required for the scaling constant (k)
(0 to 3 places).
Return to
– Input source measured in F
– Input source measured in C
frame.
Block to Configure