EN
Installation
Burner lower than tank
Burner lower than tank
y
Burner higher than tank
Burner higher than tank
H
Y must be kept as lower as possible in order to avoid cavitation. Anyway Y< 4 m.
Altitude (m)
0-500
501-800
801-1300
1301-1800
1801-2200
e.g.: altitude 1100m Theoretical H = 1m actual H 2m, Corrected H for suction 2 + 1 = 3m Corrected H for charging 2 - 1 = 1m.
Choose the Ø of the piping from the table, based on the length expanded between the tank and pump. If corrected H for suction
exceeds 4m; make provisions for a transfer pump (max. pressure 2 bar).
14
www.ecoflam-burners.com
- Oil feeding and suction line
x
Correction of altitude
Pump in suction (H +) or charging (H -)
Theoretical H (m)
FEEDING LINE WITH DANFOSS BFP21
H
(m)
0,5
1
H = x-y
1,5
2
2,5
3
3,5
N.B. = X < 20 m
H
(m)
0,5
1
1,5
2
2,5
3
3,5
0
0,5
1,0
1,5
2,0
FEEDING LINE WITH DANFOSS BFP11 R3
Length pipe (m)
ø 6 mm
ø 8 mm
ø 10 mm
19
60
21
66
23
72
25
79
27
85
29
91
31
98
Length pipe (m)
ø 6 mm
ø 8 mm
ø 10 mm
15
47
13
41
11
34
9
28
7
22
5
15
-
9
!
The length of the tubes apply to
burners powered by 50 Hz mains
electricity; in case of 60 Hz power,
divide the relevant lengths by 1.5.
420010518600
100
100
100
100
100
100
100
100
99
84
68
53
37
22