Connecting

5.1

Connecting measuring sensors

Introduction
You can connect current transmitters to the 2AI 4WIRE HS analog input modules to act as:
● Connecting 4-wire transducers.
In this chapter you will find out how to connect the measuring encoders and what to watch
out for when doing so.
Cables for analog signals
You should use shielded and twisted-pair cables for the analog signals. This reduces the
effect of interference. You should ground the shield of the analog cables at both ends. If
there are differences in potential between the cable ends, an equipotential bonding current
that may interfere with the analog signals will flow across the shield. If this is the case, you
should only ground the shield at one end of the cable.
Analog input modules
The analog input modules are galvanically isolated:
● Between the logic and backplane bus
● No isolation: Link between M
Connecting measuring encoders to analog inputs
There can be only a limited potential difference U
lines M- of the input channels and the reference point of the measuring circuit M
ensure that the permitted value is not exceeded, you must take different steps depending on
the whether the encoders are isolated or non-isolated. The steps you have to take are
described in this chapter.
2AI I 4WIRE HS analog electronic module (6ES7134-4GB62-0AB0)
Manual, 01/2008, A5E01076124-02
Note
Ensure that this difference in potential U
is a possibility of exceeding the permitted value, establish a connection between terminal
M
and the central grounding point.
ANA
and central grounding point
ANA
does not exceed the permitted value. If there
ISO
(common mode) between the measuring
CM
5
. To
ANA
23