TM000/020/060/080N
RM000/020/060/080N
Mechanical Installation
Wiring Diagrams
Analog or PWM
Digital – 3 wire / 2 position
2.2 K
1
2
TB1
COMMON (-)
24 Vac (+)
Special consideration for Digital control
In this mode, the actuator is sensitive to induced electrical voltages from external sources. To prevent such interference, if the signal
on pins 4 and 3 on TB1 are from an external 24 Vac source, install a resistor 2.2kohm, 0.5W between pins 4 and 1 and another of
2.2kohms, 0.5W between pins 3 and 1 of TB1. These resistors are included.
Input Signal and Feedback setup
Analog Mode
Digital & PWM
Mode
www.neptronic.com
2.2 K
3
4
5
FEEDBACK
DRIVE CCW
DRIVE CW
Input Signal
Input Signal is set with Dipswitch # 3
DS1-3 at OFF = 2 – 10Vdc (default setting)
DS1-3 at ON = 4 – 20mA
No Input Signal Setting
DS1-3 MUST be at OFF
Specification & Installation Instructions
Manually close the damper blades and positioned the
1.
actuator at 0º or 90º.
Slide the actuator onto the shaft.
2.
Tighten the nuts on the "U" bolt to the shaft with a 10mm
3.
wrench to a torque of 150 in.lb. [17 Nm].
Slide the mounting bracket under the actuator. Ensure free
4.
movement of the slot at the base of the actuator. The bracket
pin must be placed in the mid distance of the slot.
Fix the bracket to the ductwork with #8 self-tapping screws.
5.
Digital signal
Digital – 4 wire / 3 point floating
Feedback is set with Dipswitch #4
Feedback
DS1-4 at OFF = 4 – 20mA (default setting)
DS1-4 at ON = 2 – 10Vdc
2

Advertisement

loading

This manual is also suitable for:

Tm020nTm060nTm080nRm000nRm020nRm060n ... Show all