13 Network connection

13 Network connection

13.1 Network settings

The network interface has the following default settings:
IP address: 192.168.2.1
Subnet screen: 255.255.252.0
The default settings can be changed. See the eSy-Web operat-
ing instructions.

13.2 Connecting the network

1. Connect the network plug and cables with the electrical
connection X2 of the product.
2. Change the IP address using the web server.

13.3 Resetting the network settings

1. Ensure that the "ON-Site" DIP switch 8 is not in the "ON"
position.
2. Press and hold down the "OPEN" button 9 for at least 8 s.
ð LED 1 flashes fast in blue.
3. Press the "INIT/CLOSE" button 10.
ð Network settings are reset in the default settings.

14 Commissioning

14.1 Commissioning on the device

1. Ensure that the "ON-Site" DIP switch 8 is not in the "ON"
position (see "Buttons for on-site control", page 6).
2. Press and hold down the "INIT/CLOSE" button 10 for at
least 8 s.
ð Initialization of the actuator begins.
3. Green and orange LEDs flash alternately.
ð Initialization is completed.
ð Commissioning is completed.

14.2 Commissioning via the eSy-Web web interface

● See separate eSy-Web operating instructions.

14.3 Commissioning via digital input

ü The function of input 3 is set to init.
1. Apply 24 V DC signal briefly (max. 2 s) to connection X3
pin 6 (reference GND connection X3 pin 4).
ð Initialization of the actuator begins.
2. Green and orange LEDs flash alternately.
ð Initialization is completed.
ð Commissioning is completed.
GEMÜ 549 eSyDrive

15 Operation

15.1 Operation on the device

15.1.1 Moving the valve to the open position
1. Move the "ON-Site" DIP switch 8 to the "ON" position (see
"Buttons for on-site control", page 6).
ð Control on the device is activated.
2. Press the "OPEN" button 9.
ð The valve moves slowly to the open position.
3. Also press the "INIT/CLOSE" button 10.
ð The valve moves quickly to the open position.
ð If the valve is fully opened, the high visibility LEDs are
lit in green.
4. Move the "ON-Site" DIP switch 8 to the "OFF" position.
ð Control on the device is deactivated.
ð The valve is in the open position.
15.1.2 Moving the valve to the closed position
1. Move the "ON-Site" DIP switch 8 to the "ON" position.
ð Control on the device is activated.
2. Press the "INIT/CLOSE" button 10.
ð The valve moves slowly to the closed position.
3. Also press the "OPEN" button 9.
ð The valve moves quickly to the closed position.
ð If the valve is fully closed, the high visibility LEDs are lit
in orange.
4. Move the "ON-Site" DIP switch 8 to the "OFF" position.
ð Control on the device is deactivated.
ð The valve is in the closed position.

15.2 Operation via the web server

See separate "eSy-Web" operating instructions.

15.3 Manual override

Rotating cover!
▶ Risk of crushing.
1. Disconnect the power supply.
2. Turn housing cover 3 clockwise.
3. Remove housing cover 3.
38 / 47
WARNING
Disconnect the power supply before
using the manual override.