E1/EL01 – Comms Error
Condition – Indoor and outdoor unit do not receive feedback from one another
Installation Checks (first time running)
Check that there is 240v onto both units (indoor and outdoor).
Check wiring for continuity
If using the 4 core wiring method make sure the W terminal has been moved to 1(L)
Check the S connection from the terminal block at the outdoor unit is connected ok onto the outdoor PCB. Make sure to check
all jack plugs
Check power connections from terminal blocks to both indoor and outdoor PCBs
Make sure all other connections (controllers etc) are correct
Service Checks (system has been commissioned)
Has there been any recent work done to the building? Any power cuts etc? Any mains supply works?
Check both units have 240v and are powered correctly