Download Print this page

Honeywell NOTIFIER XP6-MA Installation And Maintenance Instructions page 3

Six zone interface module

Advertisement

from the end of wire, sliding the bare end of the wire under the clamping
plate screw.
3.
Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the first module (between 01 and 154).
In Class B operation, the remaining modules are automatically assigned to the
next five higher addresses. For example, if the base address switch is set to 28,
the next five modules will be addressed to 29, 30, 31, 32 and 33.
The module is shipped in Class B position, remove shunts for Class A. When
operating in Class A, alternate modules are paired together (+0/+1, +2/+3,
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the
modules while 29, 31 and 33 are available to be used for other modules on the
SLC. For Class A and B operation, DO NOT set the lowest address above 154,
as the other modules will be assigned to nonexistent addresses.
NOTE: The XP6-MA must have power cycled for shunt changes to take effect.
NOTE: Some panels support extended addressing. In order to set the module
above address 99 on compatible systems, carefully remove the stop on the
upper rotary switch (see Figure 7). If the panel does not support extended ad-
dressing, do not set the lowest address above 94.
4.
A shunt is provided to disable a maximum of two unused modules in
Class B operation and Class A operation. Modules are disabled from the
highest address and work downward. If two modules are disabled, the
lowest four addresses will be functional, while the highest two will be
disabled. For example, in Class B operation, if the shunt for Address Dis-
able is placed on "two" and the base switch is set to 28, the modules will
be assigned to 28, 29, 30 and 31 while disabling the highest two positions.
NOTE: Place unused shunts on single pin to store on board for future use.
FIGURE 8. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B
3.9K EOL
RESISTOR
(INCLUDED)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGUR 10.
FROM PANEL OR
PREVIOUS DEVICE
TO NEXT DEVICE
1.
To use a common power supply between multiple XP6-MA modules, connect a long power supply jumper from T5 or T6 to T5 or
T6 on the adjacent XP6-MA module.
FIGURE 9. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A
1.
To select Class A, remove the
two shunts from the "A/B se-
lect" positions.
2.
To use a common power
supply
between
multiple
XP6-MA modules, connect
a long power supply jumper
from T5 or T6 to T5 or T6 on
the adjacent XP6-MA mod-
ule.
CONNECT MODULES TO
LISTED COMPATIBLE
NOTIFIER CONTROL
PANELS ONLY
+
+
CLASS B IDC (TYPICAL)
(+)
(–)
+
+
POWER-LIMITED
SIGNAL LINE CIRCUIT 32 VDC MAX.
AND SUPERVISED
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CONNECT MODULES TO LISTED COMPATIBLE
NOTIFIER CONTROL PANELS ONLY
+
+
CLASS A IDC (TYPICAL)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
(+)
SWITCHED TO RESET THE DETECTORS.
(–)
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGURE 10.
+
FROM PANEL OR
PREVIOUS DEVICE
+
TO NEXT DEVICE
SIGNAL LINE CIRCUIT 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
POWER-LIMITED
FOR WIRE REQUIREMENTS.
AND SUPERVISED
NOTE: Power must not be applied to the unit when changing functionality on
the shunts.
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or FPLP cable as
required by Article 760 of the NEC.
• All wiring must be in accordance with the NEC, NFPA 72 and all other
applicable codes and standards. All external power supplies must be
power limited with battery back-up. All external power supplies and
detectors must be UL listed for fire protection signaling applications.
PROGRAMMING
Connect the module to listed-compatible control panels only. Refer to panel
installation documentation to confirm compatibility.
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.
FIGURE 7.
5
4
3
2
1
TENS
BASE ADDRESS
6 7 8 9
5
4
3
2
1
0
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
IDC 2
IDC 3
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
Detectors must be UL Listed compatible with the module. Install detectors
per manufacturer's installation instructions.
3
7 8
9
6
10
11
12
13
14
0
15
6 7 8 9
5
4
3
2
1
0
STATUS
INDICATORS
BASE ADDRESS
6 7 8 9
6 7 8 9
5
5
10
4
4
11
3
3
12
2
13
2
1
1
14
0
0
15
STATUS
INDICATORS
C0227-00
C0154-02
C0160-01
I56-1806-010
7/1/2022

Advertisement

loading