Press to toggle between the two choices. Stop at the
BASIC
ADVANCED:
desired test.
Basic Walk Test - Allows a single operator to run audible tests on the panel.
All logic equation automation is suspended during the test. All ACS
devices will default to Disable. They may be enabled by selecting
DISABLE ACS BOARDS
Advanced Walk Test - Allows field-supplied output point programming
that will react to input stimuli such as CBE and logic equations. When
points are activated in advanced testing, each initiating event will latch the
input. Release of the latch and subsequent activation of the next point is
controlled through use of the
default to disable. They may be enabled by selecting
soft key on the Walk Test Menu screen. An advanced test is
ACS BOARDS
audible.
/
This soft key is for future use. Walk test is audible.
SILENT
AUDIBLE:
An audible test is intended for pull station verification, magnet-activated tests on input devices, input and output device and wiring operation/verifica-
tion. Only devices previously configured to participate and designated as part of the test through the following screens will make sound.
Scroll through the choices. Stop at the desired parameter.
PARAMETER:
Toggle between
DISABLE ACS BOARDS:
5.4.1 Walk Test Activation Indications
FlashScan Poll Mode
Once the
soft key has been pressed:
START TEST
Each intelligent addressable input device will blink its address in red, and each intelligent addressable output device will blink its address in
green. Pattern examples are given below.
An input device activated in Walk Test latches on steady green for the duration of the test. If the device is put in trouble (for instance, the detector
head is removed, then replaced), the LED will be latched on for the duration of the test.
An output device activated in Basic Walk Test will remain active and the LED will glow steady green for
– 4 seconds for alarms.
– 8 seconds for troubles.
An output device activated in Advanced Walk Test will remain active and the LED will glow steady green until the
pressed.
CLIP Poll Mode
Once the
soft key has been pressed:
START TEST
Intelligent addressable input and output devices continue to blink red as usual until activated.
An input device activated in Walk Test latches on steady red during activation. If the device is put in trouble (for instance, the detector head is
removed, then replaced), the LED will be latched on for the duration of the test.
An output device activated during Basic Walk Test will remain active and the LED will glow steady green (if a FlashScan module) or steady red
(if a CLIP module) for
– 4 seconds for alarms.
– 8 seconds for troubles.
An output device activated in Advanced Walk Test will remain active and the LED will glow steady green (if a FlashScan module) or steady red
(if a CLIP module) until the
Conventional Devices
Monitor modules with the Type Codes SMOKE CONV, HEAT DETECT, and SMOKE DETECT, and outputs with the Type Code FORM C RESET do
not participate in Walk Test other than blinking their addresses if they are polled in FlashScan mode unless they are used with a FlashScan zone mod-
ule. To prevent the occurrence of false alarms for conventional devices, 24 volt power will be interrupted for up to a minute after Walk Test has been
exited.

5.4.2 Battery Checks and Maintenance

Maintenance-free sealed lead-acid batteries used in the system do not require the addition of water or electrolyte. These batteries are charged and main-
tained in a fully charged state by the main power supply's charger during normal system operation. A discharged battery typically reaches the voltage
of 27.6 VDC within 48 hours; the charge rate depends on the battery size (2.0A for 18-26AH; 5.0A-5.7A for 26AH-200AH).
66
soft key on the Walk Test Menu screen.
soft key. All ACS devices
NEXT TEST
NO
and
. This setting allows the operator to enable/disable AC devices during Walk Test.
YES
NO
Address
Blink Pattern
8
8 blinks, long stop, 8 blinks, long stop, ...
37
3 blinks, stop, 7 blinks, long stop, 3 blinks, stop, 7 blinks, long stop, ...
152
15 blinks, stop, 2 blinks, long stop, 15 blinks, stop, 2 blinks, long stop, ...
soft key is pressed.
NEXT TEST
at the
NO
at the
DISABLE
NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 0 , 2 0 1 8
W A L K T E S T
B A S I C / A D V A N C E D : B A S I C
S I L E N T / A U D I B L E : A U D I B L E
P A R A M E T E R : Z O N E
D I S A B L E A C S B O A R D S : Y E S
Walk Test Menu Screen
NEXT TEST
A C C E P T
B A C K