Download Print this page

Accessories; Maintenance; Technical Data; Designed Lifetime - Honeywell krom schroder 03250831 Operating Instructions Manual

Pressure switch for gas dg..c

Advertisement

▷ For the DG..VC, the switching point is adjustable
via hand wheel.
1
2
4
5

Accessories

See Technical Information DG (D, GB, F) –
www.docuthek.com

Maintenance

We recommend a function check once a year, or
every six months if operated with biogas.

Technical data

Safety information, see Safety manual DG
(D, GB) – www.docuthek.com
Ambient conditions
Enclosure:
IP 54 pursuant to DIN EN 60529 with standard
socket pursuant to DIN EN 175301-803,
IP 00 with AMP plug.
Safety class: 1.
This unit is not suitable for cleaning with a high-
pressure cleaner and/or cleaning products.
Maximum medium and ambient temperatures:
DG..C: -20 to +70°C (-4 to +158°F),
DG..CT: -15 to +60°C (5 to 140°F).
Long-term use in the upper ambient temperature
range accelerates the ageing of the elastomer ma-
terials and reduces the service life (please contact
manufacturer).
Transport temperature = ambient temperature.
Storage temperature: -20 to +40°C (-4 to +104°F).
Mechanical data
Gas type: natural gas, town gas, LPG (gaseous),
flue gas, biogas (max. 0.1 %-by-vol. H
3
Max. inlet pressure p
600 mbar (8.5 psig).
Max. test pressure for testing the entire system:
temporarily < 15 min. 2 bar (29 psig).
Diaphragm pressure switch, silicone-free.
Diaphragm: NBR.
Housing: glass fibre reinforced PBT plastic with
low gas release.
Lower housing section: AlSi 12.
Weight: 60 g (2.12 oz).
Recommended tightening torques:
Screw terminals in socket: 35 Ncm
Cover screw: 45 Ncm
Socket: 45 Ncm
Electrical data
Conductor diameter: 0.5 to 1.8 mm
(AWG 24 to AWG 13).
Switching capacity:
DG..C, 24 – 250 V AC:
I = 0.05 – 5 A at cos φ =1,
I = 0.05 – 1 A at cos φ = 0.6.
DG..C..G, 5 – 250 V AC:
I = 0.01 – 5 A at cos φ =1,
I = 0.01 – 1 A at cos φ = 0.6.
DG..C..G, 5 – 48 V DC: I = 0.01 – 1 A.
DG..VCT, 30 – 240 V AC:
I = 5 A at cos φ = 1,
I = 0.5 A at cos φ = 0.6.
DG..VCT..G, < 30 V AC:
I = 0.1 A at cos φ = 1,
I = 0.05 A at cos φ = 0.6.
RoHS compliant.

Designed lifetime

This information on the designed lifetime is based on
using the product in accordance with these operating
instructions. Once the designed lifetime has been
reached, safety-relevant products must be replaced.
Designed lifetime (based on date of manufacture)
in accordance with EN 1854 for pressure switches:
Medium
Gas
Air
You can find further explanations in the applicable
rules and regulations and on the afecor website
(www.afecor.org).
This procedure applies to heating systems. For
thermoprocessing equipment, observe local regu-
lations.
GB-5
= withstand pressure =
max
Designed lifetime
Switching cycles
Time [years]
50,000
250,000
S) and air.
2
10
10

Advertisement