Honeywell NOTIFIER NFS2-3030 Manual page 3

Hide thumbs Also See for NOTIFIER NFS2-3030:
Table of Contents

Advertisement

Terminal
Block/
Description
Connector/
LED
TB1
Security or Alarm Relay
TB2
Supervisory or Alarm Relay
TB3
Trouble Relay
TB4
Alarm Relay
TB5*
EIA-232 Printer/PC/CRT (Terminal)
Connection
TB6
Accessory Power
TB7*
EIA-485 ACS Connection
TB9
EIA-485 RDP Connection
J1*
Network/Service Connection (NUP)
J2
LCD Connection
J4
Backlight Connection
J5
Trouble Bus Connection
J6
Security Switch Connection
J7*
SLC Loop Control and Expander
Module Connection
J9
Keypad Connection
J13
Power Connection
J14
Future Use
J15
USB B - VeriFire Tools Connection
SW1
Security Switch
SW2
Supervisory Switch
SW3
Acknowledge Switch
SW4
Signal Silence Switch
SW5
System Reset Switch
SW6
Lamp Test Switch
Table 1 CPU2-3030(CPU2-3030DC for Canada only) Wiring Connections (1 of 2)
NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022
• Power-limited (Class 2) only if connected to a power-limited source
• Voltage and Current: Rated 2.0 A at 30 VDC resistive
• Can be changed from Security to Alarm via SW1
• Non-supervised
• Power-limited (Class 2) only if connected to a power-limited source
• Voltage and Current: Rated 2.0 A at 30 VDC resistive
• Can be changed from Supervisory to Alarm via SW2
• Non-supervised
• Power-limited (Class 2) only if connected to a power-limited source
• Voltage and Current: Rated 2.0 A at 30 VDC resistive
• Non-supervised
• Power-limited (Class 2) only if connected to a power-limited source
• Voltage and Current: Rated 2.0 A at 30 VDC resistive
• Non-supervised
• Power-Limited (Class 2)
• Supervised
• Isolated printer connection (left side)
• Isolated PC/CRT or Keltron printer supervision connection (right side)
• Equipment must be located in the same room within 20 feet of the panel with cables encased
in conduit
• Nominal Voltage: 24 VDC, Regulated
• Maximum Current: 5amp max, depending on power supply source
• Ground Fault Impedance: 0 ohms
• Supported by battery backup during AC power loss
• Power-limited (Class 2)
• Provide power to accessories located within the same enclosure
• If the accessory being powered has outputs, the outputs must be power-limited
• Class B wiring supervise with a power supervision relay or EOLR-1
• Characteristic Impedance: 120 ohms
• Supervised
• Power Limited (Class 2)
• Connection for devices such as the UDACT/UDACT-2 and annunciators
• Up to 32 annunciator devices can be connected or a total of 3,072 annunciator points
• Characteristic Impedance: 120 ohms
• Supervised return
• Power-limited (Class 2)
• Connection for devices such as the LCD-160/C or LCD-80/LCD2-80
• Power Limited (Class 2)
• Supervised
• Connection for the main display (LCD)
• Connection for the LCD backlight
• Trouble monitoring connection for auxiliary equipment
• Connection for a Security Tamper Switch (STS-1) or local control (AKS)
• Connection for the addition of LCM-320 loop control modules and LEM-320 loop extension
modules
• Uses cable P/N 75565
• Connection for the display keypad
• Non-power-limited
• Uses cable P/N 75637
• Connects to TB1 on the AMPS-24/E power supply
• If power supply is located in another enclosure, cable must be encased in conduit
• Power supply enclosure must be within 20 feet of fire panel enclosure to accommodate cable
length
• Do not use at this time
• USB connection for VeriFire Tools communication to the panel (Standard B)
• Used to toggle TB1 between Security and Alarm operation
• Used to toggle TB2 between Supervisory and Alarm operation
• Service level Acknowledge switch for local operation without a keypad/display
• Service level Signal Silence switch for local operation without a keypad/display
• Service level System Reset switch for local operation without a keypad/display
• Service level Lamp Test switch for local operation without a keypad/display