ACS Point Mode
...will, when pressed after a Page Enable, allow PAGE
PAGE
INACTIVE paging from that source. The Special Paging
INACTIVE
Function map programming at the DVC will receive the page
function.
...will, when pressed after a Page Enable, allow Page Evac
PAGE EVAC
paging from that source. The Special Paging Function map
programming at the DVC will receive the page function.
...will, when pressed after a Page Enable, allow Page Alert
PAGE ALERT
paging from that source. The Special Paging Function map
programming at the DVC will receive the page function.
....will, when pressed:
FFT-NFN
• Notify a DVC in the map format Nxxx,Nxxx,NxxxLyyMzzz or
Nxxx,Nxxx,NxxxAyyT to open the FFT-NFN link and turn on
the mapped FFT point or riser. A second press will notify the
DVC to turn off that FFT point or riser and determine whether
the FFT-NFN link should be closed or remain open.
• Notify a DVC in the map format Nxxx,Nxxx to close or open
the FFT-NFN link between two DVCs.
CO MONITOR
... will show the current state of the CO element for the
specified point entered.
CAUTION: DISABLED/ENABLED OUTPUTS
!
WHEN A DISABLED OUTPUT IS ENABLED, IT WILL BE AFFECTED BY CONDITIONS PRE-EXISTING IN THE SYSTEM.
FOR EXAMPLE, WHEN A CONDITION EXISTS IN THE SYSTEM THAT WOULD NORMALLY TURN THE OUTPUT ON,
THE OUTPUT WILL TURN ON WHEN IT IS ENABLED.
When programming an ACS point with a mode of Control, the following Control Point Select screen will be displayed:
Control Source field entry formats may be:
SLC Modules: NxxxLyyMzzz.
xxx = FACP node number
yy - the SLC loop number
zzz - module loop address
General Zones*: NxxxZyyy.
xxx = FACP node number
yyy = General zone number (Z001 - Z999, not Z000. Zone 0 is not valid).
Panel Circuit Modules: NxxxPyy.z.
xxx = FACP node number
yy = panel circuit module number
z = panel circuit push button number
Prioritized Audio Matrix (PAM) Speaker Points: NxxxIyyyyAzzSn xxx =
the DVC node number
yyyy = the input number in the PAM
zz = the DAA address on the Digital Audio Loop (01 through 32)
n = the DAA speaker circuit (1 through 4).
NOTE: A zone with a node number of zero (0) will be a local zone.
*DO NOT MIX GENERAL ZONES WITH OTHER SOURCE TYPES FOR AN ACS CONTROL POINT. Program up to eight general zones or up
to eight other control point types.
NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022
Function: The point...
Table 3 ACS Point Mapping: Explanation of Point Modes (2 of 2)
Explanation
The Point Active LED is lit if a corresponding mapped point is
active. The Status (trouble) LED is on when a point or zone is in
trouble.
The Point Active LED is lit if a corresponding mapped point is
active. The Status (trouble) LED is on when a point or zone is in
trouble.
The Point Active LED is lit if a corresponding mapped point is
active. The Status (trouble) LED is on when a point or zone is in
trouble.
The Point Active LED is lit if a corresponding mapped point is
active. The Status (trouble) LED is on when a point or zone is in
trouble.
The Point Active LED is lit if a corresponding mapped point is
active. The Status (trouble) LED is on when a point is in trouble.
This point is specifically used to annunciate the CO element of the
FIRE/CO detector.
C O N T R O L P O I N T S E L E C T
N 0 0 0 I 0 0 0 1 A 0 0 S 1
x x x
x x x
x x x
Control Point Select Screen
x x x
x x x
x x x
x x x