Introduction
This installation guide provides instructions for
installation, startup and adjustment. To receive a
copy of the instruction manual, contact your local
Sales Office or view a copy at www.fisher.com. For
further information refer to: Type Y696 Instruction
Manual, D101770X012.
PED Categories
This product may be used as a safety accessory with
pressure equipment in the following Pressure Equipment
Directive categories. It may also be used outside of the
Pressure Equipment Directive using sound engineering
practice (SEP) per table below. For information on the
current PED revision see Bulletin: D103053X012.
ProDuCt sIzE
DN 40 and 50 / NPS 1-1/2 and 2
Specifications
Body sizes and End Connection styles
See Table 1
Maximum allowable Inlet and outlet Pressures
1.0 bar / 15 psig
Proof test Pressure
All Pressure Retaining Components have been
proof tested per Directive.
Control Pressure ranges
See Table 2
temperature Capabilities
Nitrile (NBr): -29 to 82°C / -20 to 180°F
fluorocarbon (fKM): 4 to 149°C / 40 to 300°F
Perfluoroelastomer (ffKM): -18 to 149°C /
0 to 300°F
Ethylenepropylene (EPDM): -29 to 135°C /
-20 to 275°F
Installation
!
Only qualified personnel should install
or service a backpressure regulator.
Backpressure regulators should be
installed, operated and maintained
in accordance with international and
applicable codes and regulations and
Emerson Process Management regulator
technologies Inc. instructions.
1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.
CatEgorIEs
fluID tyPE
I
(1)
(1)
(1)
WarNINg
If the regulator vents fluid or a leak
develops in the system, it indicates
that service is required. failure to
take the backpressure regulator out
of service immediately may create a
hazardous condition.
Personal injury, equipment damage
or leakage due to escaping fluid or
bursting of pressure-containing parts
may result if this backpressure regulator
is overpressured or is installed where
service conditions could exceed the limits
given in the Specifications section, or
where conditions exceed any ratings of
the adjacent piping or piping connections.
to avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
1
code, regulation or standard) to prevent
service conditions from exceeding limits.
additionally, physical damage to
the backpressure regulator could
result in personal injury and property
damage due to escaping fluid. To
(1)
avoid such injury and damage, install
the backpressure regulator in a
safe location.
Clean out all pipelines before installation of the
regulator and check to be sure the regulator has not
been damaged or has collected foreign material during
shipping. For NPT bodies, apply pipe compound to
the external pipe threads. For flanged bodies, use
suitable line gaskets and approved piping and bolting
practices. Install the backpressure regulator in any
position desired, unless otherwise specified, but be
sure flow through the body is in the direction indicated
by the arrow on the body.
It is important that the backpressure
regulator be installed so that the vent
hole in the spring case is unobstructed
at all times. for outdoor installations,
the backpressure regulator should be
located away from vehicular traffic and
positioned so that water, ice and other
foreign materials cannot enter the spring
case through the vent. avoid placing the
backpressure regulator beneath eaves
or downspouts, and be sure it is above
the probable snow level.
Type Y696
Note

Advertisement

loading

Summary of Contents for Emerson Y696

  • Page 1 Sales Office or view a copy at www.fisher.com. For hazardous condition. further information refer to: Type Y696 Instruction Personal injury, equipment damage Manual, D101770X012. or leakage due to escaping fluid or...