6 Electrical connection

6.1 Power supply voltage

- The transmitter type TR must be supplied with 24 V DC, 2-wire technique.
- Terminal voltage 14 to 30 V DC (terminals 1 and 2)
- Recommendation: 2-wire cables, twisted and shielded
(cable diameter 6-12 mm)
- Ground cable shield according to section 16.1 Wiring diagram.
- In order to ensure safe HART
minimum load with R
- For the maximum amount of line and load resistance, see diagram below.
The maximum load depends on the supply voltage.
1000
800
600
400
200
0
14