Tripp Lite SmartOnline S3MX Owner's Manual page 58

3-phase ups systems
Hide thumbs Also See for SmartOnline S3MX:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
7. UPS Operation
Step 4
Turn OFF the Q3 Output breaker.
Step 5
Single input model:
Turn OFF the Q1 Input 1 breaker.
Dual input models (Optional):
Turn OFF the Q1 Input breaker and Q2 Input breaker.
Step 6
The UPS will enter Shutdown Mode and will slowly de-energise. After the UPS powers off, turn OFF the battery breaker
(external battery cabinet).
Step 7
The critical load is now supported in Maintenance Bypass Mode.
Q3
Output
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/200 kVA) Models
Q1
Input 1
S3M100KX
S3M120KX
(100 kVA/200 kVA) Models
Q1
Input 1
Q2
Input 2
S3M100KXD
S3M120KXD
(100 kVA/200 kVA) Models
Turn OFF the Q3 Output breaker.
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
Single input model:
Turn OFF the Q1 Output breaker.
(160 kVA/200 kVA) Models
Dual input models (Optional):
Turn OFF the Q1 Input breaker, Q2 Input breaker.
(160 kVA/200 kVA) Models
58
Q3
Output
Q1
Input 1
S3M160KX
S3M200KX
Q1
Input 1
Q2
Input 2
S3M160KXD
S3M200KXD

Advertisement

Table of Contents
loading

Table of Contents