Maintenance Bypass Operation; Transfer Critical Load From Line Mode To Maintenance Bypass - Tripp Lite SmartOnline S3MX Owner's Manual

3-phase ups systems
Hide thumbs Also See for SmartOnline S3MX:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
7. UPS Operation

7.3 Maintenance Bypass Operation

Follow the below steps to transfer to maintenance bypass for power stage maintenance and UPS protection.

7.3.1 Transfer Critical Load from Line Mode to Maintenance Bypass

Confirm Bypass Mode is enabled via the LCD display menu prior to performing the Maintenance Bypass procedure.
Remove the mechanical locking plate securing the Q4 Maintenance Bypass breaker (all models).
Step 1
Confirm the UPS is operating in Bypass Mode.
Step 2
Step 3
Turn ON the Q4 Maintenance Bypass breaker (all models).
Q4
Maintenance Bypass
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/120 kVA) Models
ON
OFF
Q4
Maintenance Bypass
S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kVA/120 kVA) Models
57
Q4
Maintenance Bypass
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models
2018/01/01
OFF
ON
Q4
Maintenance Bypass
S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kVA/200 kVA) Models