Current Dual-Lite PLD7 Installation, Operation And Service Instructions page 3

Emergency led battery pack

Advertisement

SW INDICATOR
ILLUSTRATION 3
UL SWITCH
COVER
Mounting Height: This product meets or exceeds the NFPA minimum light
requirements with all loads, down to the smallest rated lamp load, at heights
up to 25.8ft. Many factors influence emergency illumination levels, such as the
93071446
lamp load selected, luminare design, and environmental factors, therefore end
use verification is necessary. For installations where the attached luminaire
is mounted at heights greater then 25.8ft, the level of illumination must be
measured in the end application to ensure the requirements of NFPA 101 and
local codes are satisfied.
Step 5.
Select correct wiring diagram to connect the emergency driver to the LED load, AC LED driver and Switch. Make sure all connections are in accordance
with the National Electrical Code and any local regulations.
Step 6.
Install the labels "CAUTION" & "STATUS" in a visible location (see illustration 4).
Step 7.
After installation is complete, supply AC power to the emergency ballast and join the converter battery connector.
Step 8.
At this point, power should be connected to both the AC driver and the emergency driver, and the charging indicator light should illuminate indicating
the battery is charging.
Step 9.
A short-term discharge test may be conducted after the emergency ballast has been charged for one hour.
Step 10. Charge for 24 hours before conducting a long-term discharge test. Refer to "Operation" section below
Note: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required.
The emergency ballast must be fed from the same branch circuit as the AC ballast.
EMERGENCY DRIVER AND AC DRIVER MUST BE FED FROM THE SAME BRANCH CIRCUIT
TYPICAL SCHEMATICS ONLY. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS
EMERGENCY BACK-UP & AC DRIVER
EMERGENCY BACK-UP & AC DRIVER
RED
RED
RED
RED
WHT/RED
PLD7
WHT/RED
BLACK
PLD10
BLACK
EM LED
VIOLET (+)
EM LED
VIOLET (+)
BROWN (-)
DRIVER
BROWN (-)
DRIVER
WHITE
WHITE
WHT/BLK
WHT/BLK
BLUE
BLUE
YEL/BLK
YEL/BLK
YELLOW
YELLOW
LED (+)
LED LOAD
LED (+)
LED LOAD
LED (-)
LED (-)
AC DRIVER (-)
AC DRIVER (-)
AC DRIVER
AC DRIVER (+)
AC DRIVER
AC DRIVER (+)
BLACK
BLACK
WHITE
WHITE
LARGE
BUSHING
PLASTIC
TUBE
TY-WRAP
93071446
SMALL
BUSHING
CONVERTER BATTERY CONN.
CONVERTER BATTERY CONN.
WALL SW
WALL SW
HOT
VIOLET (+)
TEST SW/LED INDICATOR
VIOLET (+)
BROWN (-)
TEST SW/LED INDICATOR
BROWN (-)
COMMON
EM DRIVER
TYPICAL LED
LIGHTING
FIXTURE
WIRING
EMERGENCY BACK-UP, AC DRIVER
HOT
PLD7
EM LED
DRIVER
COMMON
LED LOAD
AC DRIVER
"STATUS"
LABEL
ILLUSTRATION 4
AND STEP DIMMING
RED
CONVERTER BATTERY CONN.
RED
BLACK
VIOLET (+)
VIOLET (+)
BROWN (-)
BROWN (-)
WHT/RED
WHITE
WHT/BLK
BLUE
YEL/BLK
YELLOW
LED (+)
LED (-)
AC DRIVER (-)
AC DRIVER (-)
AC DRIVER (+)
AC DRIVER (+)
SW 1
WHITE
LINE 1
LINE 2
SWITCH
INDICATOR
93071865
"CAUTION"
LABEL
LED mtg plt
(lens not shown)
HOT
TEST SW/LED INDICATOR
COMMON
HOT
SW 2