System Charge For Various Matched Systems; Cooling Capacity - With Air Handler Coils; Cooling Capacity - Upflow, Downflow & Horizontal Furnaces And Coils (Coil Only Ratings) - Coleman TCHE36S43S1 Technical Manual

Split system air conditioners
Table of Contents

Advertisement

5371957-CTG-D-0120

SYSTEM CHARGE FOR VARIOUS MATCHED SYSTEMS

Outdoor Unit
1,2
Required TXV
3,4,5
Indoor Unit
FC38C
FC49D
Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil
only matches, please see the "COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils" table.
FOOTNOTES:
1. For applications requiring a TXV use S1-1TVM*** series kit.
2. A TXV kit must be used with these indoor units to obtain system performance.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require 60 second time delay.
4. CF and FC coils cannot be used in horizontal applications.
5. Charge adders shown above do not indicate that coils are rated for every application. Refer to Performance Data Tables for actual performance for specified
system matches. Obtain certified system ratings from www.ahridirectory.org.
PROCEDURES:
1. Check the Factory Unit Charge listed on the unit nameplate to verify the refrigerant charge for the outdoor unit, the smallest matched indoor unit,
and the 15 feet of interconnecting lineset.
2. Verify the indoor metering device and additional charge required for the specific matched indoor unit in the system using the above table.
3. Add additional charge for the amount of interconnecting lineset greater than 15 feet at the rate specified in the Physical and Electrical Table.
4. For installations requiring additional charge, weigh in refrigerant for the specific matching indoor unit and actual lineset length.
5. Once the charge adders for matched indoor unit and for lineset have been weighed in, verify the system operation against the temperatures and pressures in
the Charging Chart for the outdoor unit. Locate Charging Charts on the outdoor unit and also in the Service Data Application Guide on
www.simplygettingthejobdone.com.
device in the system, and allow ten minutes after each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match
the Charging Chart.
6. Permanently stamp the unit data plate with the TOTAL SYSTEM CHARGE defined as follows: TOTAL SYSTEM CHARGE = Base Charge (as shipped) +
charge adder for matched indoor unit + charge adder for actual lineset length + charge adjustments to match the Charging Chart.

COOLING CAPACITY - With Air Handler Coils

UNIT
MODEL
MODEL
TCHE36S4(3,4)S1
ME16CN21
TCHE36S4(3,4)S1
MVC16CN21
TCHE36S44S1
ME12CN41
TCHE36S44S1
ME16CN41
TCHE48S4(3,4)S1
ME14DN21
TCHE48S4(3,4)S1
ME20DN21
TCHE48S44S1
ME20DN41
TCHE48S4(3,4)S1
MVC14DN21
TCHE48S4(3,4)S1
MVC20DN21
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ANSI/AHRI Standard 210/240.
Cooling MBH based on 80°F entering air temperature, 50% RH (Relative Humidity), and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTUs at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTUs during a normal annual usage period for cooling divided by the total
electric power input in watt-hours during the same period.
1. CM coils available with a factory installed horizontal drain pan. See price pages for specific model number.
— = Not applicable.
MP Modular Air Handlers use Coil Only Ratings.
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT MODEL
TCHE36S4(3,4)S1
TCHE48S4(3,4)S1
For rated condition information, see the footnotes below the System Capacity - Single Piece and Modular Air Handlers table.
1. Systems matched with furnaces or air handlers not equipped with blower-off delays may require 60 second time delay.
— = Not Applicable.
MP Modular Air Handlers use Coil Only Ratings.
PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Ratings.
4
Follow the Subcool or Superheat charging procedure in the Installation Manual according to the type of indoor metering
AIR HANDLER
WIDTH
21.0
21.0
21.0
21.0
24.5
24.5
24.5
24.5
24.5
COIL
MODEL
WIDTH
FC38C
21.0
FC38C
21.0
FC49D
21.0
FC49D
21.0
TCHE36S4(3,4)S1
BA2
Additional Charge, Oz
0
COIL
RATED
1
MODEL
CFM
FC38C
1200
FC38C
1200
FC38C
1250
FC38C
1100
FC49D
1425
FC49D
1425
FC49D
1400
FC49D
1175
FC49D
1375
CFM RANGE
RATED
(MIN.-MAX.)
CFM
1000 - 1400
1200
1000 - 1400
1200
1400 - 1800
1425
1400 - 1800
1425
TCHE48S4(3,4)S1
BA2
0
COOLING
NET MBH
SEER
TOTAL
SENS.
36.00
27.20
16.00
35.80
27.20
15.50
36.00
28.40
16.00
36.00
26.80
16.00
46.50
34.60
15.10
46.50
34.60
15.50
46.50
34.80
15.25
45.50
31.80
15.50
46.50
34.20
15.50
COOLING
NET MBH
SEER
TOTAL
SENS.
35.6
27.2
35.6
27.2
46.0
33.8
46.0
33.8
Johnson Controls Ducted Systems
EER
13.00
12.75
13.00
13.00
12.50
12.50
12.50
12.75
12.75
1
EER
14.00
12.20
14.00
12.20
14.00
12.15
14.00
12.15