Trane IntelliPak with Symbio 800 Programming Manual page 54

20 to 75 tons with the td7 display
Hide thumbs Also See for IntelliPak with Symbio 800:
Table of Contents

Advertisement

TD7 Display
Table 18. Ventilation override modes
Value
VOM A Supply Fan
VOM A Supply Fan Speed
VOM A Relief Fan/Dampers
VOM A Outdoor Air Damper
VOM A VAV Box Relay
VOM A Ventilation Override Relay
VOM A Lock
VOM B Supply Fan
VOM B Supply Fan Speed
VOM B Relief Fan/Dampers
VOM B Outdoor Air Damper
VOM B VAV Box Relay
VOM B Ventilation Override Relay
VOM B Lock
VOM C Supply Fan
VOM C Supply Fan Speed
VOM C Relief Fan/Dampers
VOM C Outdoor Air Damper
VOM C VAV Box Relay
VOM C Ventilation Override Relay
VOM C Lock
VOM D Supply Fan
VOM D Supply Fan Speed
VOM D Relief Fan/Dampers
VOM D Outdoor Air Damper
VOM D VAV Box Relay
VOM D Ventilation Override Relay
VOM D Lock
VOM E Supply Fan
VOM E Supply Fan Speed
VOM E Relief Fan/Dampers
VOM E Outdoor Air Damper
VOM E VAV Box Relay
VOM E Ventilation Override Relay
VOM E Lock
54
Settings (Factory Default)
Off (Off, On)
Min (Min, Max, Auto)
Off/Closed (Off/Closed, On/Open)
Closed (Closed, Open)
De-energized (De-energized,
Energized)
De-energized (De-energized,
Energized)
Not Locked (Not Locked, Locked)
On (Off, On)
Max (Min, Max, Auto)
Off/Closed (Off/Closed, On/Open)
Open (Closed, Open)
Energized (De-energized, Energized)
Energized (De-energized, Energized)
Not Locked (Not Locked, Locked)
Off (Off, On)
Min (Min, Max, Auto)
On/Open (Off/Closed, On/Open)
Closed (Closed, Open)
De-energized (De-energized,
Energized)
Energized (De-energized, Energized)
Not Locked (Not Locked, Locked)
On (Off, On)
Max (Min, Max, Auto)
On/Open (Off/Closed, On/Open)
Open (Closed, Open)
Energized (De-energized, Energized)
Energized (De-energized, Energized)
Not Locked (Not Locked, Locked)
On (Off, On)
Auto (Min, Max, Auto)
On/Open (Off/Closed, On/Open)
Open (Closed, Open)
Energized (De-energized, Energized)
Energized (De-energized, Energized)
Not Locked (Not Locked, Locked)
Description
Factory Default Settings - Unit Off
All components are commanded off
and closed.
VOM A has highest priority, will
override B, C, D, and E.
Factory Default Settings - Pressurize
Over pressurizes the space to prevent
air infiltration from
outside the space.
VOM B has higher priority than C, D,
and E.
Factory Default Settings - Relief
Performs an exhaust function to
remove air from the space.
VOM C has higher priority than D, and
E.
Factory Default Settings - Purge
Exchanges the air in the space with
fresh air.
VOM D has higher priority than E.
Factory Default Settings - Purge w/
Discharge Air Pressure Control
Exchanges the air in the space with
fresh air while performing duct
static pressure control within a
multizone application.
VOM E has lowest priority.
RT-SVP011E-EN