Errors; Errors After An Initialization Run - Baelz Automatic 373-E07 Operating Instructions Manual

Motorized linear actuator
Table of Contents

Advertisement

Motorized Linear Actuator

7.6 Errors

7.6.1 Errors after an initialization run

Following a successful initialization run, only the green LED is lit.
If the red LED is flashing, this indicates an error following an unsuccessful initialization run.
The first error to occur during initialization is shown. If the green LED is lit, the unit had already
been initialized before the current initialization run. If the green LED is flashing, the unit had not
been successfully initialized previously.
The red LED shows errors occuring during initialization as follows:
Error code 1:
interval
Error code 2:
etc. up to ...
Error code 8:
etc..
Error code
Error
Invalid status of initialization run. Possible
1 → 1 x
cause: EMI (electromagnetic interference).
Sensor malfunction at analogue input AI1:
2 → 2 x
No signal from potentiometer.
3 → 3 x
Potentiometer value at AI1 too small.
Possible cause: EMI.
Potentiometer value at AI1 too large.
4 → 4 x
Possible cause: EMI.
Wrong direction of travel
5 → 5 x
Obstruction: potentiometer or motor not moving. Check connections, set N↔S switch to "N",
6 → 6 x
7 → 7 x
Stroke too long.
Stroke too short.
8 → 8 x
Following an initialization run, the red LED shows only initialization errors as long as DIP switch
12 is set to 1. This enables a clear differentiation between errors occuring during initialization
and those occuring during normal positioner operation. Setting DIP switch 12 from 1 back to 0
permits the red LED to show any normal operational errors instead of initialization errors which
may have occured.
W. Baelz & Sohn GmbH & Co. · Koepffstrasse 5 · 74076 Heilbronn · Germany · www.baelz.de
interval
etc.
interval
interval
interval
etc.
interval
Corrective action
Remove source of interference.
Check connection terminals 91, 92, 93
(see wiring diagram, Fig. 24, page 22).
Replace potentiometer if necessary.
Remove source of interference.
Replace potentiometer if necessary.
Remove source of interference.
Replace potentiometer if necessary.
Check motor (97, 98, 99) and potentiometer
(91, 92, 93) connections (see wiring diagram,
Fig. 24, page 22).
Remove source of interference.
remove any obstructions.
Fit actuator to a valve with nominal stroke
length < 22 mm.
Fit actuator to a valve with nominal stroke
length > 8,7 mm, remove any obstructions.
baelz 373-E07
Seite | Page
29 |
36

Advertisement

Table of Contents
loading