Freestyle 2 Series Manual page 92

Table of Contents

Advertisement

FreeStyle
®
2
series
37 Troubleshooting
Make sure to determine the causes of outages. Do not leave the boiler operating without a com-
plete diagnosis.
FreeStyle
Control diagnosis
®
1. The boiler control is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will flash together with
the fault symbol (see Table 3 or 4) indicating the fault code.
2. Certain faults cause permanent boiler shutdowns (marked with the letter "A" see Table 3): to restore operation, press the RESET
button (Item 6 - Figure 80, page 62) for 1 second or RESET on the optional remote timer control if installed; if the boiler fails
to start, it is necessary to firstly eliminate the fault.
3. Other faults (indicated with the letter "F", see Table 4, page 95) cause temporary shutdowns that are automatically reset as soon
as the value returns within the boiler's normal operating range.
Protection and error conditions
1. Several checks are included to protect the boiler and its environment. Severe error will cause a lockout condition which can only
be cleared by the reset key at the boiler front panel.
2. Non severe errors faults will reset as soon as the cause of the problem disappears/corrects themselves.
3. Number of reset action is limited to 5 in 24 hours. By powering off/on, it is possible to reset this limitation: in this way, another
5 reset per 24 hour can be done.
4. Error codes can be divided in 2 groups:
a. Manual Reset type lockout codes – "A" codes: (which blocks the heat demand - Press reset button for 1 second to reset)
b. Automatic Reset type lockout codes – "F" codes: (cause temporary shutdowns that are automatically reset as soon as the
value returns within the boilers normal working range)
Hard Lock-out condition codes
Lock out condition is given with the capital "A" (alarm) on the status display and error code on the
temperature display. The meaning of the error numbers are as follow:
Table 3
"A" codes – Hard Lock-out
Error code Description
A01
No burner ignition after five attempts
A02
False flame indication
High limit protection: pump does not run or no
A03
water circulation
A04
F07 repeated 3 times in the last 24 hours
A05
No frequency feedback from fan after 1 hour
A06
6 times flame loss in 4 minutes time frame
A16
Outside sensor is not connected
Nominal water pressure not reached within
A23
maximum allowed time
A26
F40 repeated 3 times in the last hour
Temperature sensor not or bad connected to
A41
the pipe (CH mode)
Too high difference between two CH supply water
A42
temperature sensors
Temperature sensor not or bad connected to
A44
the pipe (DHW mode)
A61
Flame circuit error
A62
Gas valve circuit
A63
E2 prom error
A65
ADC circuit error
92
-
wall mount gas
fired water boiler
(continued)
Manual Reset
boiler manual
Abbreviation
Description
ADC
Analog Digital Converter
CH
Central Heating
DHW
Domestic Hot Water
LP
Liquefied Petroleum (Propane) Gas
LWCO
Low Water Cut Off
MMI
Machine Interface- Control Interface
OTC
Outdoor Temperature Sensor
PCB
Printed Circuit Board - Control board
Pulse width modulation - Used for
PWM
modulating pumps and motors
Part number 550-142-950/0122

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Freestyle 2 Series

This manual is also suitable for:

Fs-80 ngFs-80 lpFs-120 ngFs-120 lpFs-155 ngFs-155 lp

Table of Contents