Freestyle 2 Series Manual page 109

Table of Contents

Advertisement

FreeStyle
®
2
series
37 Troubleshooting
Figure 138
Troubleshooting suggestions for
Category
Description
Flame current supervision
Flame current supervision
Flame current supervision
System
System
System
Fan Regulation
Fan Regulation
Fan Regulation
Fan Regulation
Heat exchanger protection
DHW Config. 2
DHW Config. 2
System
System
System
Chimney material
Chimney material
Chimney material
Wind condition
Wind condition
Wind condition
DHW Config. 2
DHW Config. 2
DHW Config. 2
DHW Config. 2
DHW Config. 2
Flame current supervision
Part number 550-142-950/0122
-
wall mount gas
fired water boiler
(continued)
FreeStyle
E2 prom parameters
Num. Address
Description
142
ML – 80D5
Flame current on level1 offset
143
ML – 80DB
Flame current on level2 offset
144
ML – 8112
Flame current off level offset
145
ML – 8134
High altitude & Chimney length selection
146
ML – 8131
Pre-purge time between A01 attempts
147
ML – 80D6
Pump protection time
148
CL5 – 0AC8
FAN Kp Up
149
CL5 – 0AF4
FAN Ki Up
150
CL5 – 1B8C
FAN Kp Down
151
CL5 – 1BB0
FAN Ki Down
152
ML – 80DD
Heat exchanger protection
153,2
ML – 80D2
Priority Over Ride Set
154,2
ML – 80D3
Priority Over Ride Reset
161
ML – 80D7
Fan type selection
162
ML - 8121
High limit protection timer
163
ML – 80D4
OTC Exempt
165
ML – 8110
PVC/CPVC Selection
166
ML – 8132
PVC maximum temperature
167
ML – 8133
CPVC maximum temperature
168
ML - 8135
Wind condition time
169
ML - 8136
Wind condition frequency
170
ML - 8137
Wind condition ADC
171,2
ML – 8111
DHW thermostat/sensor selection
172,2
ML – 80C7
DHW tank prepare mode
173,2
ML – 80D1
DHW Delta
174,2
ML – 80CC
DHW slope control
175,2
ML – 813F
Hydraulic configuration
176
CL5 – AAA1
Offset flame current low limit
boiler manual
®
boilers — Fault displays and diagnostics
(continued)
Unit
Range
Def
Low
High
Value
ADC
0
255
3
ADC
0
255
0
ADC
0
255
20
Num
0
2
0
Min
0
60
0
Sec
0
20
5
Num
0
100
25
Num
0
255
220
Num
0
100
25
Num
0
255
250
°F/Sec
0
27
18
°F
0
240
30
°F
0
240
15
Num
0
1
1
Sec
0
20
10
Num
0
1
0
Num
0
2
1
°F
140
212
190
°F
158
230
200
Sec
0
60
10
Hz
0
255
110
ADC
0
255
30
Num
0
1
0
Num
0
2
0
°F
0
35
18
°F/min
1
20
9
Num
0
1
0
Num
1
20
20
109

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Freestyle 2 Series

This manual is also suitable for:

Fs-80 ngFs-80 lpFs-120 ngFs-120 lpFs-155 ngFs-155 lp

Table of Contents