Freestyle 2 Series Manual page 74

Table of Contents

Advertisement

FreeStyle
®
2
series
31 Startup — Quick Start Guide using default settings
"Test Mode Operation"
1.
To start, create a demand for heat, open up a hot water faucet or turn up the thermostat.
Proceed to put the boiler into operation as follows: To operate the boiler in test mode, press the CH "-"
2.
and "+" keys together for 5 seconds (See below and Figure 104, page 79) to activate the TEST mode.
3.
The boiler lights at the maximum heating 100% rate displayed on the LCD display.
9
4.
The high fire (large) flame symbol will be displayed once the boiler has lit.
Use DHW " _ " button to drop firing rate to low fire.
5.
6.
To exit the "Test mode", press the CH keys (Items 3 and 4 Figure 80, page 62) together for 5 seconds, or
leave the boiler to automatically switch off after 15 minutes or stopping DHW flow.
7.
This TEST procedure is used to check/adjust combustion CO and CO
Figure 107, page 82 and Figure 110, page 83.
Liquefied Petroleum (Propane) Gas — Propane conversion kit (optional - sold separately, see Figure 163, page 120 .
High altitude — High altitude (over 2,000 feet) requires only changing the altitude setting on the control. (See page 70).
Digital or U-tube manometer for checking gas line pressure.
Volt-ohmmeter may be required for troubleshooting.
Combustion Analyzer to verify and adjust combustion.
This unit must only be used for its intended purpose. This unit is designed to heat water to a temperature below boil-
ing point and must be connected to a heating system and/or a water supply system for domestic use, compatible with
its performance, characteristics and heating capacity. Any other use is deemed improper.
Incorrect installation can cause damage or injury for which the manufacturer cannot be deemed responsible.
The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions
on page 86 of this manual. Failure to comply could result in severe personal injury.
Pay attention when handling the boiler insulation panels as they contain materials that could irritate the skin.
No part of the boiler contains asbestos, mercury or Chlorofluorocarbons (CFC's).
74
-
wall mount gas
fired water boiler
QUICK START GUIDE
System start
Equipment that maybe required for installation
boiler manual
(continued)
per specifications,
2
(continued)
Part number 550-142-950/0122

Hide quick links:

Advertisement

Table of Contents
loading

Related Products for Freestyle 2 Series

This manual is also suitable for:

Fs-80 ngFs-80 lpFs-120 ngFs-120 lpFs-155 ngFs-155 lp

Table of Contents