10.
Troubles and
troubleshooting
Troubleshooting on regulations and hydraulics must
be done by an authorised firm
For repairs use only original spare parts
TROUBLE
Boiler does not react
after turn on of main
switcher
Boiler does not heat or
insufficiently
heat/heating pump
works
Boiler heats but it is
very noisy
Boiler turns on quickly
Great oscillations of
working pressure
Table 8: Troubles and troubleshooting
DESCRIPTION
Display does not react,
other components do
not work
All on display are within
recommended values
but boiler does not
make hot water
Higher level of noise
during work
Reaches temperature
too quickly and turns on
Too fast and too big
changes of working
pressure
CAUSE
Boiler is out of power supply
Fuses on bottom plate are off
Vanishing of managing phase
Damage of main fuse ON/ OFF
Lack of 1 or 2 phases
Small power of boiler
Some relay damaged
Some heater damaged
Air in the system
Small water flow
Possible carbonate layer on
heater
Valves below the boiler off
Pump fuse stop to work
Pump jammed
Pump inaccurate
One valve off
Expansion dish pressure
inadequate
Inaccurate dish
Troubles and troubleshooting
MEASURE
Provide power supply
Turn on fuses
Check if fuses have three
phases on output
Change damaged part
Check all three phases
Check set power of boiler
Change damaged part
Change damaged part
Check if the system is air
vented and vent it
Check valves below boiler and
open it
Clean filter below boiler
Take out heaters and clean it
(this is not included in claims
during warranty period)
Open valves
Change inaccurate part
Start pump rotor
Change inaccurate part
Open the valve
Check pressure in expansion
dish and if needed set dish
pressure adequately
Change inaccurate part