PROFIBUS Settings

6.6. PROFIBUS Settings

6.6.1. PROFIBUS Address Settings

NOTE
Ensure that the Communicator rotary switches are sett to 000.
Figure 21. PROFIBUS address setting
In the PROFIBUS address field, enter the Communicator node address.

6.6.2. Timeout Time Settings

Figure 22. PROFIBUS page, Timeout times
Connection Timeout
Specify how long a Modbus TCP connection may be idle before it is closed by the Communicator.
The default value is 60 seconds.
Process Data Active Timeout
Specify the maximum allowed time between two incoming messages in steps of 10 ms.
If this time is exceeded, the high level network is considered to be offline.
The data sent to the sub-network is frozen.
A value of 0 disables this feature, i.e. the high level network can never go offline.
The default value is 0 ms.
SCM-1202-201 Version 1.0
®
Anybus
Communicator
- Modbus TCP Server to PROFIBUS DP Device
Page 31 of 60