3.3 WR20D‐EM Installation
Mount the relay in an easy to access location, typically at the power
voltage wiring compartment.
This Emergency relay should be installed where it can be frequently tested for EM operation, refer to local
code requirements for periodic testing.
The Wireless EM Relay (WR20D‐EM) should be mounted where the relays radio communication is not
obstructed by metal enclosures or subject to equipment with high EMF noise.
The WR20D‐EM relay must be within 50 feet line of sight to the switch stations intended to control it and that
radio transmission is not obstructed by metal.
Mount the relay to a junction box or fixture using the 1/2" nipple and secure with the 1/2" locknut provided
and mounting bracket.
Terminate the Emergency and Normal power line inputs 120/277VAC, neutrals, and fixture control load
outputs from the relay to the EM and Normal power fixtures to be controlled as required by NEC Code.
Test 0‐10VDC wiring from the fixtures for proper voltage and polarity of the DC control leads before
connecting to the WR20D‐EM relay.
Terminate the low voltage Class‐2 0‐10VDC dimming control leads using two #18AWG leads for EM and
Normal control to the fixtures. Keep Class‐2 wiring separate from line voltage runs per NEC Code
requirements.
Test the EM relay operation using the EM Test button on the relay.
To link the WR20D‐EM relay to LSG3‐W switches, refer to TB0401
For control of the WR20D‐EM from a LLEVO‐W controller refer to TB0402.