Line distance protection REL650
Version 2.2
Table 51. Loss of voltage check LOVPTUV
Function
Operate voltage
Reset ratio
Pulse timer when disconnecting all three
phases
Timers
Hitachi Power Grids
SEMOD175210-2 v7
Range or value
(0–100)% of UBase
<105%
(0.050–60.000) s
(0.000–60.000) s
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Accuracy
±0.5% of U
r
-
±0.5% ±25 ms
±0.5% ±25 ms
1MRK 506 384-BEN H