ABB Relion REL650 Series Product Manual page 71

Line distance protection
Hide thumbs Also See for Relion REL650 Series:
Table of Contents

Advertisement

Line distance protection REL650
Version 2.2
Table 51. Loss of voltage check LOVPTUV
Function
Operate voltage
Reset ratio
Pulse timer when disconnecting all three
phases
Timers
Hitachi Power Grids
SEMOD175210-2 v7
Range or value
(0–100)% of UBase
<105%
(0.050–60.000) s
(0.000–60.000) s
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Accuracy
±0.5% of U
r
-
±0.5% ±25 ms
±0.5% ±25 ms
1MRK 506 384-BEN H
71

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650 a11Rel650 a12

Table of Contents