ABB Relion REL650 Series Product Manual page 103

Line distance protection
Hide thumbs Also See for Relion REL650 Series:
Table of Contents

Advertisement

Line distance protection REL650
Version 2.2
Basic IED functions
Table 151. Self supervision with internal event list
Data
Recording manner
List size
Table 152. Time synchronization, time tagging
Function
Time tagging resolution, events and sampled measurement values
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled
measurement values
Time tagging error with SNTP synchronization, sampled measurement values
Table 153. Time synchronization PTP: IEC/IEEE 61850-9-3
Supported types of clock
Accuracy
Number of nodes
Ports supported
Table 154. IRIG-B
Quantity
Number of channels IRIG-B
Number of optical channels
Electrical connector:
Electrical connector IRIG-B
Optical connector IRIG-B
Type of fiber
Supported formats
Accuracy
Hitachi Power Grids
M11963-1 v5
Value
Continuous, event controlled
40 events, first in-first out
M12331-1 v9
GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v2
Boundary Clock (BC), Ordinary Clock (OC), Transparent Clock (TC)
According to standard IEC/IEEE 61850-9-3
According to standard IEC/IEEE 61850-9-3
All rear Ethernet ports
SEMOD141136-2 v10
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Value
1 ms
± 1.0 ms typically
± 1.0 ms typically
Rated value
1
1
BNC
Type ST
62.5/125 μm multimode fiber
IRIG-B 00x
+/- 1μs
1MRK 506 384-BEN H
103

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rel650 a11Rel650 a12