Line distance protection REL650
Version 2.2
Table 157. RI and RD type inverse time characteristics
Function
RI type inverse characteristic
1
=
×
t
k
0.236
-
0.339
I
EQUATION1137-SMALL V1 EN-US
I = I
/I
measured
set
RD type logarithmic inverse characteristic
æ
ö
I
-
ç
×
÷
5.8
1.35
In
=
t
è
ø
k
EQUATION1138-SMALL V1 EN-US
I = I
/I
measured
set
Table 158. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection
Function
Operating characteristic:
æ
ö
A
ç
÷
=
+
×
t
B k
(
)
ç
÷
-
P
I
1
è
ø
EQUATION1249-SMALL V3 EN-US
I = I
/I
measured
set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
Long Time Extremely Inverse
Long Time Very Inverse
Long Time Inverse
Hitachi Power Grids
Range or value
0.05 ≤ k ≤ 999.00
1.5 x I
≤ I ≤ 20 x I
set
set
GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v5
Range or value
0.05 ≤ k ≤ 2.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=28.2, B=0.1217, P=2.0
A=19.61, B=0.491, P=2.0
A=0.0086, B=0.0185, P=0.02, tr=0.46
A=0.0515, B=0.1140, P=0.02
A=64.07, B=0.250, P=2.0
A=28.55, B=0.712, P=2.0
A=0.086, B=0.185, P=0.02
© 2017 - 2021 Hitachi Power Grids. All rights reserved
1MRK 506 384-BEN H
Accuracy
Accuracy
105