ABB Relion REL650 Series Product Manual page 54

Line distance protection
Hide thumbs Also See for Relion REL650 Series:
Table of Contents

Advertisement

Line distance protection REL650
Version 2.2
Table 28. Power swing detection ZMRPSB
Function
Reactive reach
Resistive reach
Timers
Minimum operate current
Table 29. Power swing logic PSLPSCH
Function
Permitted maximum operating time
difference between higher and lower
zone
Delay for operation of underreach zone
with detected difference in operating
time
Conditional timer for sending the CS at
power swings
Conditional timer for tripping at power
swings
Timer for blocking the overreaching
zones trip
Table 30. Out-of-step protection OOSPPAM
Function
Impedance reach
Characteristic angle
Start and trip angles
Rotor start angle
Rotor trip angle
Zone 1 and Zone 2 trip counters
54
M16036-1 v10
Range or value
(0.10-3000.00) W/phase
(0.10–1000.00) W/phase
(0.000-60.000) s
(5-30)% of IBase
SEMOD171935-5 v5
Range or value
(0.000 — 60.0000) s
(0.000 — 60.0000) s
(0.000 — 60.0000) s
(0.000 — 60.0000) s
(0.000 — 60.0000) s
SEMOD175136-2 v9
Range or value
(0.00 - 1000.00)% of Zbase
(72.00 - 90.00) degrees
(15.00 - 130.00) degrees
(90.0 - 130.0) degrees
(15.0 - 90.0) degrees
(1 - 20)
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Accuracy
±2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x U
r
Current range: (0.5-30) x I
r
Angle: at 0 degrees and 85 degrees
±0.5% ± 10 ms
±1.0% of I
r
Accuracy
±0,2% or ±15 ms whichever is greater
±0,2% or ±15 ms whichever is greater
±0,2% or ±15 ms whichever is greater
±0,2% or ±15 ms whichever is greater
±0,2% or ±15 ms whichever is greater
Accuracy
/(√3 ⋅ I
±2.0% of U
)
r
r
±5.0 degrees
±5.0 degrees
±5.0 degrees
±5.0 degrees
-
1MRK 506 384-BEN H
Hitachi Power Grids