Question 1: What is FLA? Answer: Full load amps
Question 2: What is MCA? Answer: Minimum circuit ampacity. This is used to help determine
the wire size.
Question 3: What is MOP? Answer: Maximum Overcurrent Protection device. This is to help
determine the maximum protective device.
Question 4: What is the input voltage tolerance? Answer: In general it is +/- 10% but refer to
Electrical Section for more details.
Question 5: Will all units operate at 50 or 60 hertz power? Answer: No. This depends on the
model and options selected. Consult with Data Aire for details.
Question 6: Does the unit require an electrical ground? Answer: Yes. All units require a true
earth ground.
Question 7: What size field wire size is required to connect to unit? Answer: Refer to National
Electric Code for wire ampacities size.
Question 8: Does the condensate pump require separate power source? Answer: Ceiling unit
with unit mounted condensate pump is powered by the unit.
Question 9: Can I install an Emergency Power Off (EPO) switch, and if so, where is it
installed?
Answer: Yes, an Emergency power Off (EPO) switch can be installed. Refer to the electrical
diagrams and locate the terminal strip that is designated as the Remote Shutdown Dry
Contacts.