Hot Gas Lines; Liquid Lines; Suction Lines; Table 2 Hot Gas Lines (Inches Od) - Data Aire DAPA-2.5 Installation, Operation & Maintenance Manual

Mini-plus ceiling systems
Table of Contents

Advertisement

Hot Gas Lines

50 (15.2)
Unit
Tonnage
Horizontal &
Vertical Down
2.5
5/8
3
5/8
4
7/8
5
7/8

Liquid Lines

Unit
Tonnage
2.5
3
4
5

Suction Lines

Unit
50 (15.2)
Tonnage
Horizontal &
Vertical Down
6
7/8
8
7/8
10
7/8
13
7/8

Table 2 Hot Gas Lines (Inches OD)

Equivalent Feet (Meters)
100 (30.5)
Vertical
Horizontal &
Vertical Down
Up
5/8
5/8
5/8
5/8
5/8
7/8
7/8
7/8

Table 3 Liquid Lines (Inches OD))

50 (15.2)
100 (30.5)
3/8
1/2
1/2
1/2

Table 4 Suction Lines (Inches OD)

Equivalent Feet (Meters)
100 (30.5)
Vertical
Horizontal &
Vertical Down
Up
7/8
7/8
7/8
7/8
7/8
1-1/8
7/8
1-1/8
NOTICE:
1. If equivalent piping length falls between two columns above, choose
the longer equivalent length.
2. If hot gas line refrigerant flow is upward, use "Vertical Up".
3. If hot gas line refrigerant flow is downward, use "Horizontal & Vertical
Down".
150 (45.7)
Vertical
Horizontal &
Vertical Down
Up
5/8
5/8
5/8
7/8
5/8
7/8
7/8
7/8
Equivalent Feet (Meters)
150 (45.7)
1/2
1/2
1/2
5/8
1/2
5/8
5/8
5/8
150 (45.7)
Vertical
Horizontal &
Vertical Down
Up
7/8
7/8
7/8
7/8
7/8
1-1/8
7/8
1-1/8
21
200 (61.0)
Vertical
Horizontal &
Vertical Down
Up
5/8
7/8
5/8
7/8
5/8
7/8
7/8
7/8
200 (61.0)
1/2
5/8
5/8
5/8
200 (61.0)
Vertical
Horizontal &
Vertical Down
Up
7/8
7/8
7/8
7/8
7/8
1-1/8
7/8
1-1/8
Vertical
Up
5/8
5/8
5/8
7/8
Vertical
Up
7/8
7/8
7/8
7/8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dapa-03Da pa-04Dapa-05