Condensate Pump Side Mounting Pump (Optional)

NOTES:
1. Condensate pump can be mounted in other places, for example units with a vertical supply-
return air plenum.
2. The suction line of the pump needs to be lower than the drain line of the unit.
L1 = Minimum 1" (25.4 mm)
L2 = Fan static pressure x 1.5
3. Bracket (Data Aire P/N 550-021-006) to be mounted to the unit and stainless-steel tank (Data
Aire P/N 550-721-464) are factory provided.
4. Hose, hose clamps, self-drilling sheet metal screws #10 x 3/4", fittings, P-trap and copper
tubing are field provided.

Figure 5 Typical Side Pump Mounting