Heat Exchanger Phase Check; Ghrc Air-Cooled Heat Exchanger Phase Check; Darc Heat Exchangers Phase Check; Line Set Charge Calculations - Data Aire DAPA-2.5 Installation, Operation & Maintenance Manual

Mini-plus ceiling systems
Table of Contents

Advertisement

An out of phase fixed speed scroll compressor will draw relatively low amps and both suction and
discharge pressures will remain nearly equal. If necessary, reverse any two of the three input line
voltage wires at the line voltage field connection point to change the compressor rotation.
Units shipped from the factory are run tested to ensure the compressor rotation is consistent with
evaporator fan motor. However, a field changeout of a compressor may require checking proper phase.

Heat Exchanger Phase Check

GHRC Air-Cooled Heat Exchanger Phase Check

Air-cooled GHRC condensers and GHRU condensing unit heat exchangers are only offered in three
phase voltages and the individual axial EC fan motors will only operate in one direction but the rotation
of the compressor on GHRU units must be checked. See the GHRC Air-Cooled Condensers
Installation, Operations and Maintenance Manual for additional information regarding this type of heat
exchanger.

DARC Heat Exchangers Phase Check

See the DARC Air-Cooled Condensers Installation, Operations and Maintenance Manual for proper
phase check procedures.

Line Set Charge Calculations

1. Since most of the refrigerant weight is in liquid form in the liquid line, refrigerant in the hot
gas line and suction line is ignored in the charging calculation.
2. Calculate the total of the liquid line run, then multiply the equivalent feet of the line based on
the line size by the correct multiplier to get the refrigerant weight needed for the line-set.
Liquid Line Nominal
Size (inches)
3/8
1/2
5/8
3/4
1
Example: If the liquid line of an R-410A system is 150 feet of 1-1/8" OD tube, then
multiply
Example: model DAPA-2.5XX (6.0 + 57.06 lbs.) * 0.80 = 50.5 lbs.

Table 11 Liquid Line Multiplier

Liquid Line Size
OD (inches)
1/2
5/8
3/4
7/8
1-1/8
Note: Charge Weight is calculated at 77F (25C).
150 * 0.387 = 57.06 lbs.
R-410A
Multiplier
0.068
0.109
0.157
0.243
0.387
48
R-407C
Multiplier
0.073
0.117
0.167
0.259
0.413

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dapa-03Da pa-04Dapa-05

Table of Contents

Save PDF