contact, intended to be used in a control circuit not exceeding 5 amps at 24 VAC. Use field supplied
Class 1 wiring.
These programmable output contacts will close on a failure and remain closed until the alarm is no
longer present. The terminal designations for these alarm output contact pairs are:

Remote Sensors

The Mini-dap4 panel comes with combination remote mounted temperature and humidity sensor for
field installation. The sensors are attached to standard 35 feet (11 m) of cable and come mounted in a
remote sensor enclosure. The temperature and humidity sensors require a total of four wires and the
provided cable is twisted, shielded type cable. Optional 50 feet (15 m) to 150 feet (46 m) length of
cables are available.

Condensate Pumps

The optional condensate pumps which ships loose, normally require a separate source of 110-volt
power. Always check the pump power requirements before connecting power. Condensate pumps are
available in other voltages.
Condensate pumps may also come unit mounted and wired in the unit as a factory option. While no
outside power source is required, field piping is still a requirement.

Disconnect Switch (Optional)

A thru door locking disconnect switch is an optional feature which includes a non-automatic disconnect
switch mounted in the high voltage section of the electrical control box. The operating mechanism
prevents access to the high voltage electrical components until switched to the "OFF" position. The
operating mechanism protrudes through the exterior door and is lockable in the OFF position.

Table 10 Remote Alarm Contacts Terminals

TB1
15
Remote Alarm (Common)
14
Remote Alarm 1 (Normally Open)
16
Remote Alarm 1 (Normally Closed)
NOTICE: The optional disconnect switch extension shaft and locking handle
are shipped loose to prevent damage during transit and installation. It is the
installing contactors responsibility to install these components as part of the
installation process.