VALVE
Solenoid valves must be connected between the "+" and "-" terminals. The negative terminal is not
directly connected to ground. This output is driven by 12 V and will only work with 12 V valves.
EGND
This terminal must be connected to the same ground as the pilot and main burner assemblies. Modules
come pre-wired with a connection to the enclosure ground lug.

2.5 | Enclosure Specifications

The Ion Pilot card is mounted in the EPX enclosure.
SPECIFICATIONS
Dimensions
Hazloc Rating
Mounting
Enclosure Construction
Operating Temperature
Storage Temperature
Standards: Complies with IEC 60079-0:2011, 6th Edition and IEC 60079-1:2014, 7th Edition
EPX ENCLOSURE
Top Width 11.7 cm (4.61 in)
Base Width 16.8 cm (6.63 in)
Height 21.7 cm (8.53 in)
Depth 13.3 cm (5.25 in)
Class I, Div 1, GRP BCD, Type 4X; Class I, Zone 1, AEx d IIB +
H2 T6 Gb; Ex db IIB+H2 T6 Gb, IECEx
Channel Bar or Direct Mount
Aluminum
-40°C to 60°C
-40°C to 60°C
8