I-Bx Chiller Only Non-Reversible Inverter Air/Water Units - Mitsubishi Electric i-BX-N Technical Manual

Table of Contents

Advertisement

TM_i-BX(-N)_NC05_00_06_20_EN
8.2

I-BX CHILLER ONLY NON-REVERSIBLE INVERTER AIR/WATER UNITS

Chiller only i-BX units have the following parameter values:
130Z Reversible = NO
130X Unit only Chiller or HP = Only chiller
pCO size
Thermostatic valve
Compressors
Analogue Inputs
Connector
Type
B1
NTC
B2
NTC
B3
-
B4
NTC
J3
B5
4-20 mA
B6
-
B7
NTC
B8
-
B9
-
J18
B10
4-20 mA
B11
NTC
B12
NTC
FREE
4
(opt) optional in relation to the factory configuration
(3) Enable with parameter 0314 or automatic enable of the probe if boiler or
delivery heater enabled.
Digital Inputs
Connector
Type
Description
ID1
/
High pressure switch (*)
ID2
/
System primary flow switch
ID3
-
N/A
Configurable:
J4
ID4
/
- ON / OFF
ID5
-
N/A
ID6
-
N/A
ID7
-
N/A
Configurable
ID8
/
- Night function
- Demand Limit
J16
ID9
-
N/A
Configurable:
ID10
/
Dehumidifier
FREE
5
(*) ONLY FOR i-BX(-N) 35 THREE-PHASE or for units with PSD1 drivers
MEHITS S.p.A.
TECHNICAL MANUAL
Medium
Electronic
1
Description
System exchanger water input
System exchanger water output
N/A
External air temperature (Machine)
High pressure
N/A
Inertial storage tank temperature (opt)
(3)
N/A
N/A
Low pressure
Compressor delivery temperature
Compressor intake temperature
Analogue Outputs
Connector
Type
Y1
-
Y2
-
PWM /
J5
Y3
0-10V
DC
Y4
0-10V
DC
FREE
2
(*) The Y3 analogue output is used to manage the modulating
fan. The output can be controlled in two modes: 0/10V or
phase cut (for MCHRTF regulators).
The working mode is set using parameter 136L (0/10V or
phase cut).
Selecting "phase cut" will make parameters 136M, 136N and
136O available. These parameters can be used to set the triac
for the control of the MCHRTF device.
Digital Outputs
Connector
Type
NO1
-
NO2
-
J12
NO3
/
NO4
-
J13
NO5
/
NO6
-
J14
NO7
/
NO8
-
NO9
-
NO10
-
J15
NO11
-
NO12
-
FREE
8
67
Version NC05 - Translation of the Original Instructions
Description
N/A
N/A
AC/EC fan (*)
LT1 mixed valve
Description
N/A
N/A
System exchanger antifreeze
heater
N/A
System pump
N/A
Configurable:
- Alarm
- Dehumidifier
N/A
N/A
N/A
Configurable:
Dehumidifier
N/A

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-bx

Table of Contents