EXTERNAL AIR TEMPERATURE AND WATER TEMPERATURE

The heat pump is inhibited (compressor startup inhibition) when the water temperature reaches the maximum value set through parameter 0636
near the air temperature set using parameter 133E. This value will change dynamically (according to the band set with parameter 133H),
decreasing in proportion to the decrease of the external air temperature (differential set with parameter 133F), in accordance with the function
described below.
In order to allow a limitation of the air temperature produced even at high temperatures, similarly to what just described, it will also be possible to
set parameters "133R, "133S" and "133T" in accordance with the function described below:
The probe is configured using parameter
External air T
(B6)
air temperature differential
(133S)
Air temperature threshold for
the start of the reduction of
the
produced
water
temperature due to inhibition
of the heat pump
(133R)
Low
air
temperature
threshold for the start of the
reduction
of the produced
water temperature due to
inhibition of the heat pump
(133E)
air temperature differential
(133F)
If the compressor is on in adjustment mode, the unit will continue to operate normally, in accordance with the active protections (envelope control,
temperature limits, pressure control).
MEHITS S.p.A.
TECHNICAL MANUAL
.
P132Z
Heat pump inhibition
water temperature
proportional band 2
(133T)
Heat pump inhibition
water temperature
proportional band
1
(133H)
Heat pump inhibition max
water temperature
(0636)
54
Version NC05 - Translation of the Original Instructions
Water T
(B1/B2)