Remote Starter Display Wiring; Control Power Wiring - Daikin DWSC079 Installation, Operation And Maintenance Manual

Single/dual compressor centrifugal chillers
Table of Contents

Advertisement

Remote Starter Display Wiring

Remote mounted Wye-Delta, solid state, and across-the-line starters require field
wiring to activate the optional ammeter display or the full metering display on the
chiller's operator interface panel. The wiring is from the D3 board in the starter to
the compressor controller and to the bias block; both located in the compressor
control panel.
Wiring Connection on Starter for Optional Display
Figure 13, Field Wiring for Optional Display

Control Power Wiring

The control circuit on the Daikin centrifugal packaged chiller is designed for 115-volts. Control power can be supplied
from three different sources:
1.
If the unit is supplied with a factory-mounted starter or VFD, the control circuit power supply is factory-wired
from a transformer located in the starter or VFD.
Option
D–EIMWC00808-16HU - 30/64