Daikin DWSC079 Installation, Operation And Maintenance Manual page 14

Single/dual compressor centrifugal chillers
Table of Contents

Advertisement

Figure 3, Minimum Entering Condenser Water Temperature (EXV)
65,0
60,0
55,0
50,0
45,0
40,0
35,0
30,0
0
For example; at 44F LWT, 10 degree F Delta-T, and 50% full load operation, the entering condenser water temperature
could be as low as 44.5F. This provides excellent operation with water-side economizer systems.
Depending on local climatic conditions, using the lowest possible entering condenser water temperature may be more
costly in total system power consumed than the expected savings in chiller power would suggest, due to the excessive
fan power required.
Cooling tower fans must continue to operate at 100% capacity at low wet bulb temperatures. As chillers are selected
for lower kW per ton, the cooling tower fan motor power becomes a higher percentage of the total peak load chiller
power.
Even with tower fan control, some form of water flow control, such as tower bypass, is recommended.
Figure 5 illustrates two temperature actuated tower bypass arrangements. The "Cold Weather" scheme provides better
startup under cold ambient air temperature conditions. The check valve may be required to prevent entraining air at the
pump inlet.
D–EIMWC00808-16HU - 15/64
Minimum Entering Condenser Water Temperature - 10 F Range
44
LChWT
42
LChWT
10
20
30
40
Min. ECWT = 5.25 + 0.88*(LWT) - DT
ECWT = Entering condenser water temperature
LWT = Leaving chilled water temperature
DT
= Chilled Water Delta-T at full load
FL
PLD = The percent chiller load point to be checked
50
60
70
80
Percent Load
(PLD/100) + 22*(PLD/100)
FL*
90
100
110
2

Advertisement

Table of Contents
loading

Table of Contents