Note: 1. Chilled water and condenser connection location can vary. Check markings on unit or consult unit
certified drawings for connection locations on specific units.
Location and Mounting
The unit must be mounted on a level concrete or steel base and must be located to provide service clearance at one end
of the unit for possible removal of evaporator tubes and/or condenser tubes. Evaporator and condenser tubes are rolled
into the tube sheets to permit replacement if necessary. The length of the vessel should be allowed at one end. Doors
or removable wall sections can be utilized for tube clearance. Minimum clearance at all other points, including the top,
is 3 feet (1 meter). The National Electric Code (NEC) can require four feet or more clearance in and around electrical
components and must be checked.
Operating/Standby Limits
Equipment room temperature, standby
•
Water in vessels and oil cooler: 32F to 122F (0C to 50C)
•
Without water in vessels and oil cooler: 0F to 140F (-18C to 60C) 55°C
•
WSC without water in vessels: 0F to 130F (-18C to 54.4 C)
Equipment room temperature, operating: 32F to 104F (0C to 40C)
Maximum entering condenser water temperature, startup: design plus 5 degrees F (2.7 degrees C)
Maximum entering condenser water temperature, operating: job specific design temperature