Location And Mounting; Operating/Standby Limits - Daikin DWSC079 Installation, Operation And Maintenance Manual

Single/dual compressor centrifugal chillers
Table of Contents

Advertisement

Note: 1. Chilled water and condenser connection location can vary. Check markings on unit or consult unit
certified drawings for connection locations on specific units.

Location and Mounting

The unit must be mounted on a level concrete or steel base and must be located to provide service clearance at one end
of the unit for possible removal of evaporator tubes and/or condenser tubes. Evaporator and condenser tubes are rolled
into the tube sheets to permit replacement if necessary. The length of the vessel should be allowed at one end. Doors
or removable wall sections can be utilized for tube clearance. Minimum clearance at all other points, including the top,
is 3 feet (1 meter). The National Electric Code (NEC) can require four feet or more clearance in and around electrical
components and must be checked.

Operating/Standby Limits

Equipment room temperature, standby
Water in vessels and oil cooler: 32F to 122F (0C to 50C)
Without water in vessels and oil cooler: 0F to 140F (-18C to 60C) 55°C
WSC without water in vessels: 0F to 130F (-18C to 54.4 C)
Equipment room temperature, operating: 32F to 104F (0C to 40C)
Maximum entering condenser water temperature, startup: design plus 5 degrees F (2.7 degrees C)
Maximum entering condenser water temperature, operating: job specific design temperature
Figure 2, DWDC Major Component Location
D–EIMWC00808-16HU - 12/64