Special Situations While Remote Monitoring Panel Operates; Possible Failures; Mechanical Dimensions - Tescom RMP-X1 Installation And User Manual

Ups remote monitoring panel
Table of Contents

Advertisement

Status Information
RECTIFIER START !
INVERTER START !
MAINT SWITCH ON !
MANUEL BYPASS !
STATUS ALARM !
STATUS NORMAL !
EMERGENCY STOP !
WAITING SYNC !
STATUS FAULT !
STATUS WARNING !
CLOSE BATT.CB !

3.4 Special situations while remote monitoring panel operates

If panel's communication with UPS interrupts, all values coming from UPS will be seen as "!
seconds and panel will give audio warning as very short "beep" with one minute breaks.
Short "beep" button voice is given in every press on panel buttons.
When the panel voice is turned-off on the menu, panel's audio alarm will be prevented. If a different
alarm occurs, panel voice will be opened automatically.
4.

POSSIBLE FAILURES

If electricity is not supplied to panel when the supply cable is plugged, supply cable may be failed. The
socket which the cable is plugged in may be failed. Main card transformer of remote monitoring panel
may be failed.
All connections made with UPS but if communication interrupted alarm is given on the remote
monitoring panel screen;
o
Control whether the selected communication interface is correct. RS232 / RS485
communication ports are different.
o
Cable may be failed. Plug the cable to a PC that you are sure of having functional com port
directly with UPS and try with T-mom software. If not functional, try with another CC05 cable.
o
If you are sure about the cable soundness and communication error is still available, a problem
may be available in the main card of remote monitoring panel. Inform the service.
UPS Communication is available but if measured values are false or various values cannot be read;
o
In this case, see the communication status of UPS from the "Alarms Menu".
UPS: 232 Tout P1 etc. messages will be seen. In this case, UPS's software version
will be incompatible. UPS software should be in TX100 or TX300 communication protocol.
5.

MECHANICAL DIMENSIONS

135mm
:
Rectifier started to operate.
:
Inverter started to operate.
:
Maintenance Bypass Switch is on.
:
Load manually transferred to grid.
:
Alarm status message on the lower line means alarm status situation is temporary
:
UPS operates normally.
:
Emergency shut-off button is pressed.
:
Inverter operated I am waiting for grid synchronization to transfer the load.
:
Failure status is permanent.
:
Warning status message on the lower line is a warning system functioning but, Caution!
:
UPS waits opening of accumulator switch.
280mm
12
! ! "
for 10
205mm