Actuator Specifications - Hayward RSR3 Series Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

Actuator Specifications

Torque (motor) Minimum
Torque (spring) Minimum
Minimum Required Torque
Supply Voltage/Frequency
Current Draw
Wiring Class
Angle of Rotation
Runtime (Power)
Motor Type
Runtime (Spring)
Life Cycles at 10 sec Spring
Response Time (Spring)
Control Mode
Feedback
Auxiliary Switch Rating
(2) - fixed @ 5° and 85°
Drive Configuration
Electrical Connections
Environmental Rating
Manual Override
Integral Heater
Housing Material
Physical Dimensions
Weight
Ambient Operating Range
Duty Cycle (>14 sec Mode)
Maintenance
Default Mode:
Note label identifier "R" (blue arrow). The
manual override key winds the spring in a
CCW direction, and the spring unloads in
a CW direction (default for Hayward valve
assemblies).
The RSR has a manual override built into the geartrain. Inserting the supplied allen key into
the port (black arrow above), you can manually turn the spring mechanism to WIND the spring
system. However you CANNOT UNWIND the spring system if power is present. As shown
above, the RSR has a spring CW and a spring CCW side, identified by the "L" and "R" on
their respective sides of the actuator label. Notice that the override key rotates in OPPOSITE
directions depending on which side of the actuator you are accessing.
WARNING –
the manual override allen key will NOT remain in position... once you let go of the key,
the spring WILL drive the actuator back to its unwound position.
Hayward Flow Control
Hayward Flow Control
RSR3-0
On/Off/Jog
None
None
50%
Power:
Spring:
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
www.haywardflowcontrol.com
www.haywardflowcontrol.com
RSR3-2
133"lb/15Nm
133"lb/15Nm
27"lb/3Nm
24...230vac/dc, +15% / -20% AC:50/60Hz
4.7A @ 3 sec Mode MAX
Class 1 (grounded)
95 deg including 5 deg pre-load
30 seconds @ 90 deg
Brushless DC
10 seconds @ 90 deg
Minimum 10,000 Cycles at 10 sec Spring
Up to 1 second after power failure
On/Off/Jog
None
0.1A @ 250vac / 3A @ 24vac
12mm Double Square, 100% Overload-Proof
Self-Locking up to 133"lbs/15Nm
1m Cable, Exits through 1/2" EMT Connector
NEMA 4X / IP66
Supplied Hex Key (Opt Handwheel)
Thermostatically controlled
Aluminum die casting
8.3"L x 3.7"W x 3.2"D / 210mm x 95mm x 80mm
7.8 lbs / 3.5Kg (no options installed)
Storage Temp: -40F/+158F (-40C/+70C)
Working Temp: -40F/+122F (-40C/+50C)
50%
Maintenance Free
133"lb/15Nm - 30 sec @ 90 deg
133"lb/15Nm - 10 sec @ 90 deg
Note label identifier "L" (blue arrow). The
manual override key winds the spring in
a CW direction, and the spring unloads
in a CCW direction. (non-standard for
Hayward assemblies).
RSR3 Series
RSR3-P
4-20mA or 2-10vdc IN
4-20mA or 2-10vdc OUT
None
50%
1-888-HAY-INDL (1-888-429-4635)
1-888-HAY-INDL (1-888-429-4635)
RSR3IOM Rev B ECR 043V
RSR3IOM Rev B ECR 043V
Page 4 of 9
Page 4 of 9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rsr3-0Rsr3-2Rsr3-p

Table of Contents