VACON® RS485 and CAN Bus Option Boards
Installation Guide
Table 25: FS = Fieldbus Status, Green
LED status
OFF
ON
Blinking fast (once per s)
Blinking slow (once per 5 s)

7.4 LED Indications on OPTE6 Option Board

NOTE! Older versions of OPTE6 have the Board status (N) and CANopen run (M) LEDs in different order.
N A M
Illustration 49: LED Indications on VACON
N
Board status
A
CANopen err
Table 26: N = Board Status, Green
LED status
OFF
ON
Blinking fast (once per s)
Table 27: A = CANopen err, Red
LED status
Description
OFF
No error
Blinking
Invalid configuration
58 | Danfoss A/S © 2022.08
Description
Fieldbus module is waiting for parameters from the AC drive
No external communication
Fieldbus module is activated
Parameters received and module activated
Module is waiting for messages from the bus
Module is activated and receiving messages from the bus
Module is in FAULT state
No messages from Master within the watchdog time
Bus broken, cable loose or Master off line
OPTE6 Option Board
®
Description
Option board not activated
Option board in initialization state waiting for activation command from the AC drive
Option board is activated and in RUN state
Option board is ready for external communication
M
CANopen run
Troubleshooting