Error Codes
The control module has the ability to detect problems with the valve
kit system and will initiate error codes when they occur. The error
codes listed below will guide you to solving troubleshooting issues.
Ignition Safety Error: One short beep every one second.
Cause: Pilot did not light within the trial period of 50-60 seconds
therefore step motor will turn gas valve to OFF position.
Corrective Action: Press OFF button to clear. Wait 30 seconds and
try again.
Recycle Safety Error: Two short beeps every one second.
Cause: 1. Pilot automatically lights and drops out 3-times within
2-minutes causes step motor to turn gas valve to OFF position. 2.
Someone has pressed the ON/OFF button 6-times within 2-min-
utes causing the step motor to turn gas valve to OFF position.
Corrective Action: Press OFF button to clear. After 5-minutes the
beeping will stop then retry.
Sensor Safety Error: Four short beeps every one second (constant

PRODUCT REFERENCE INFORMATION

Product Reference Information
Linear Electronic
VF Outdoor Fireplaces
Cat. No.
F4493
F4494
F4495
F4496

OPTIONAL ACCESSORIES

Cat. No.
Model#
F3502
LPK 1
LP Conversion kit for 36-inch outdoor fireplace
F3503
LPK 2
LP Conversion kit for 48-inch outdoor fireplace
F3504
LPK 3
LP Conversion kit for 60-inch outdoor fireplace
F3505
LPK 4
LP Conversion kit for 72-inch outdoor fireplace
F3507
GLO-BLACK
Black Onyx Glass Media, 5lb
F3508
GLO-CRYSTAL
Diamond Crystal Glass Media, 5lb
F3509
GLO-LT BLUE
Sapphire Blue Glass Media, 5lb
900861-00D
ERROR CODE TROUBLESHOOTING
Model
ODLVF36ZEN
ODLVF48ZEN
ODLVF60ZEN
ODLVF72ZEN
Description
beeping).
Cause: Pilot flame sensor voltage too high, ground circuit not
properly connected, pilot ground wire loose or not connected, or
motor not plugged into control module; therefore, step motor will
turn gas valve to OFF position.
Corrective Action: Press OFF button to clear. Wait 30-seconds to
thermocouple to cool down. If persist, then check other possible
causes and retry.
Thermal Safety: Four short beeps every two seconds.
Cause: System has overheated and exceeded 170°F internal tem-
perature limit and the step motor will turn gas to OFF.
Corrective Action: Internal temperature must cool down to below
160°F then press the OFF button to clear and retry.
Communication Safety: One short beep every four seconds.
Cause: Transmitter and module are not communicating properly.
Could be related to distance greater than 20-feet away from each
other or weak/dead batteries in one or the other.
Corrective Action: Module must receive a signal from transmitter.
OPTIONAL ACCESSORIES CONT.
Remote Control Kit
Cat. No.
Model#
F2687
EF-BRCK
Ecoflow Control Kits
Cat. No.
Model#
F2660
EF-WWRCK
IHP.us.com
ON
OFF
HI
LOW
ON/OFF
Continuous Pilot
Description
Remote Control, Manual ON/OFF opera-
tion, Off / Continuous pilot feature
ON
OFF
HI
LO
Description
Wireless Wall Switch, On/Off, High/Low
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Odlvf48zenOdlvf60zenOdlvf72zen

Table of Contents