Page 3
Indicates alternative voltage or current. Indicates direct voltage or current. Installation Considerations Installation and operation of Accura 3550 meter should be performed only by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Caution Failure to observe the following instructions may result in severe injury or death.
Page 4
Warning Observe the following instructions, or permanent damage to the meter may occur. Do not apply Accura 3550 to voltages and currents that exceed Input ratings of PT and Manual Rootech Inc. reserves the right to make changes in the device specifications shown in this User Guide without notice.
Page 5
Rootech’s liability shall be limited to twice the amount of the relevant purchased product. Rootech shall not be liable for any claim- other than a claim solely for the breach of one of the above warranties that is made in accordance with the above described procedures- made by the...
Page 6
Only the terms expressed in these limited Warranties shall apply and no distributor, corporation or other entity, individual or employee of Rootech or any other entity is authorized to amend, modify or extend the Warranties in any way.
Page 7
Standard Compliance CE Approved Process Control Equipment EN61326 and IEC61010 E324900 QMS-1347 KAB-QC-09 Page 7...
Page 8
Revision History The following versions of the Accura 3550 User’s Guide have been released. Revision # Revision date Description Firmware version Revision 1.0 2006. 06. 30 Initial draft Revision 1.1 2007. 04. 24 Modifying basic module recognition 1.17 Revision 1.2 2007.
Contents Chapter 1 Introduction ........................... 13 Overview ......................................13 AC/DC Measurements dedicated to Rectifier ....................13 Accuracy, Power Quality ..............................13 CE/UL Safety and Reliability ............................13 Features ......................................14 Measurement ..................................14 Power Quality ..................................14 Basic Module ..................................14 Communication .................................
Page 10
Ground Terminal ................................30 Step 5: Add a Basic Module[DC module] ........................31 Step 6: Wire a Basic Module ..............................32 DC Module ..................................32 Step 7: Wire the Power Supply and Ground Terminal of a Basic module ............. 35 Power Supply..................................
Page 11
Figures Fig 1.1 Front Side ................................18 Fig 1.2 Rear Side ................................18 Fig 1.3 Basic Module[DC Module] Rear Side ..................... 18 Fig 1.4 Front View ................................19 Fig 1.5 Rear View................................19 Fig 1.6 Side View ................................19 Fig 1.7 ANSI 4” .................................. 20 Fig 1.8 DIN96 ..................................
Page 12
Fig 2.7 DC module digital input channel 2 of rectifier fault ..............50 Fig 2.8 DC module digital input channel 3 of rectifier fault ..............51 Fig 2.9 DC module digital input channel 4 of rectifier fault ..............51 Fig 2.10 DC module digital output channel 1 setup..................51 Page 12...
Overview AC/DC Measurements dedicated to Rectifier Accura 3550 is a high accuracy digital power meter dedicated to rectifier, suited to power measurements and DC measurements. In rectifier, the existing customers obtain dc voltage and current from analog inputs of RTU after converting signals using separate tranducer. The signal conversion several times deteriorates the overall data reliability, and causes the rising of costs.
Features Measurement 64 Sampling/Cycle True RMS IEC 62053-22 Class 0.5S 50, 60Hz Phase voltage, line to line voltage, current Power, energy, power factor, frequency Fundamental component, True RMS of current 4 Quadrant Power †...
Measurements dedicated to Rectifier Rectifier panel guarantees reliability of control power in energy system during the interruption of power. Accura 3550 is a high accuracy digital power meter dedicated to rectifier, suited to power measurements, DC measurements, and rectifier status.
Parameters Realtime Average Total Maximum Minimum Phase voltage ■ ■ ■ ■ Line to line voltage ■ ■ ■ ■ Current ■ ■ ■ Power Active ■ ■ ■ Reactive ■ ■ ■ Apparent ■ ■ ■ Energy Active ■ Reactive ■...
Chapter 2 Mounting Environmental Conditions The Accura 3550 should be mounted in a dry, dirt free location away from heat sources and very high electric fields. To operate properly and effectively, environmental conditions should range within the following guidelines Items...
Before You Begin Before installing the meter, observe the instructions in this guide and read the safety precautions presented on the “Installation Considerations” page. Danger Power up after the voltage and current wiring is completed. Meter Overview Fig 1.1 Front Side Fig 1.2 Rear Side Fig 1.3 Basic Module[DC Module] Rear Side Page 18...
Step 1: Mounting Sequence Remove connector on the bottom of the meter. fit the meter into cutout[ANSI 4” or DIN96] Fig 1.7 ANSI 4” Fig 1.8 DIN96 Note The meter is mounted on switchgear boards (metal cabinet) in electrical facilities. Page 20...
Step 2: Voltage and Current Inputs Fig 1.9 Voltage and Current Connector Voltage Input Pin name Connector Terminal block Wire 2.1 to 3.5 mm [ 14 to 12 AWG] Rating 0 ~ 600V 3 ~ L-L[Line to line], 0 ~ 457V 3 ~ L-N[Line to neutral] Burden 0.02VA/phase @220V Impedance...
Wiring Diagram Using External PTs Danger Failure to observe the following wiring diagrams may result in severe injury or death. Be sure to use shorting block when connecting the meter to CT secondaries. Fig 1.10 Single Phase 2 Wires, Wiring Mode = 1P2U Warning In single phase 2 wires, be sure to use V , 1S, 1L terminals as the above.
Fig 1.11 Three Phase 3 Wire Open Delta Using 2CTs, Wiring Mode = 3P3O Warning In three phase 3 wire open delta, be sure to connect V to V as the above. Fig 1.12 Three Phase 3 Wire Open Delta Using 3CTs, Wiring Mode = 3P3O Warning In three phase 3 wire open delta, be sure to connect V to V...
Direct Diagram Using No PTs Danger Failure to observe the following wiring diagrams may result in severe injury or death. Be sure to use shorting block when connecting the meter to CT secondaries. Fig 1.14 Single Phase 2 Wire Direct , Wiring Mode = 1P2U Warning In single phase 2 wires, be sure to use V , 1S, 1L terminals as the above.
Fig 1.15 Single Phase 3 Wire Direct Using 2 CTs, Wiring Mode = 1P3U Warning In single phase 3 wires, be sure to use V , 1S, 1L, 3S, 3L terminals as the above. Fig 1.16 Three Phase 3 Wire Open Delta Direct, Wiring Mode = 3P3O Warning In three phase 3 wire open delta direct, use PTs for voltages over 457V [line to line].
Fig 1.17 Three Phase 3 Wire Open Delta Direct Using 3 CTs, Wiring Mode = 3P3O Warning In three phase 3 wire open delta direct, use PTs for voltages over 457V [line to line]. be sure to connect V to V as the above.
UL2919 cable is recommended for communication. Comm Indicator Comm LED shows green when the meter is transmitting data. Protocol The meter provides Modbus RTU protocol. Refer to the Accura 3550 Communication User’s Guide for Modbus protocol implementation details. Page 29...
Step 4: Wire the Power Supply and Ground Terminal Fig 1.20 Wiring of Power Supply and Ground Terminal Power Supply Pin name PP[+/L], PN[-/N] Connector Screw terminal[Pluggable] Wire 1.25 to 3.5 mm [ 24 to 14 AWG] Ratings AC 85 ~ 265V, 50/60Hz ~, DC 100 ~ 300V Compliance Pollution degree 2 Burden...
Step 5: Add a Basic Module[DC module] Fig 1.21 Adding of a Basic Module Warning When a basic module[DC module] is not added or recognized, SETUP LED blinks Page 31...
Step 6: Wire a Basic Module DC Module The Accura 3550 is provided with a DC module as a basic module. Fig 1.22 DC Module NC means “No Connection”. DC Voltage/Current DC voltage Recfifier current Battery current Pin name OUT+...
Page 33
Digital Input 4 Channels Ch 1 Ch 2 Ch 3 Ch 4 Pin name Ground Both of DI are internally common-connected. Connector Screw Terminal[Pluggable] Application Dry contact Wire 1.25 to 3.5 mm2[ 24 to 14 AWG] Min Pulse Width 10 ms Fig 1.24 Digital Input Digital Output 1 Channel Ch 1...
Off command “off” outputs Note Refer to “module mode” for selecting of Latch or Pulse. Fig 1.25 DC Relay application Fig 1.26 AC Relay application Note Use Clamp Diode or ZNB in order not to apply more than 350V peak to digital output. Warning Use external relay in order to control more than the maximum load, AD/DC 400V 350mA, of digital output.
Step 7: Wire the Power Supply and Ground Terminal of a Basic module Fig 1.27 Wiring of Power Supply and Ground Terminal of a Basic module Power Supply Pin name PP[+/L], PN[-/N] Connector Screw terminal[Pluggable] Wire 1.25 to 3.5 mm [ 24 to 14 AWG] Ratings AC 85 ~ 265V, 50/60Hz ~, DC 100 ~ 300V...
Chapter 3 Meter Operation/Setup Each of these functions can be accomplished by pressing the Menu, Up, Down, and Enter buttons on the front panel. Display mode View parameter measurements Setup mode Configure parameters[wiring, communication, and etc.] Reset mode Reset energy, demand, maximum, and minimum. System mode View meter system information[meter option, firmware version].
Page 38
AVG LED When the “AVG” LED is lit, fourth row LED display shows the average value of A, B, C displays. TOT LED When the “TOT” LED is lit, fourth row LED display shows the sum of A, B, C displays. x1000 LED When the “x1000”...
Page 39
Parameter displays in following order In Group B Order Parameter A, B, C Voltage THD √ Current THD √ Parameter displays in following order In Group C Order Parameter Active energy kVARh Reactive energy kVAh Apparent energy Frequency Note Energy[kWh, kVARh, kVAh] is read by the total number which join third and fourth LED display together.
Setup Mode In Setup mode, You can setup menus, such as PT/CT ratio, wiring, and communication after mounting the meter. Button Functions in Setup Mode Button Function Enter setup mode by pressing the Up and Down buttons at the same time. Move to the previous menu screen.
Page 41
Wiring mode Single phase 2 wires Single phase 3 wires Three phase 3 wires, Open Delta Three phase 4 wires √ Comm address 1 ~ 247 Protocol Modbus RTU √ Rootech † Speed[bps] 1200bps 2400bps 4800bps 9600bps √ 19200bps 38400bps ‡...
Reset Mode In Reset Mode, you can perform a Energy reset, a Demand reset, or a Maximum/minimum reset. Energy Reset Initialize kWh, kVARh, kVAh Demand Reset Initialize all of Demand, Peak Demand Maximum/minimum Reset Initialize all of Maximum Button Functions in Reset Mode Button Function Enter reset mode by pressing the Down and Enter buttons at the...
System Mode You can view system information, such as product number, version, demand time, frequency selection, and etc. Button Functions in System Mode Button Function Enter System Mode Move to the previous menu screen. Move to the next menu screen. Enter system edit mode to configure the displayed menu value.
Page 44
Frequency 50Hz, 60Hz Reactive power calculation Method 1 √ Method 2 † Demo mode √ Serial number Version X.XX Hardware version X.XX Firmware version † When operated in demo mode, SETUP LED blinks. Page 44...
Reactive Calculation Method Rootech supports two methods for accurate calculation of reactive power. Method 1: General Calculation Method 1 is used to obtain reactive power, and apparent power by using calculation of vector apparent power. ∫ ∫ ∫ ∫ ∫...
Page 46
regeneration], power factor and active power are negative. Method 2: Calculation regarding Harmonics Method 2 is used to obtain reactive power from apparent and active power, and the overall apparent power by using calculation of vector apparent power. ∫ ∫ ∫...
Module Mode Module mode has both display and setup menus. In module display menu You can view information of module and its channels, and in module setup menu configure channels of module. Module Display Menu Button Functions in Module Mode Button Function Enter module mode.
Module Setup Menu Button Functions in Module Mode Button Function Enter module mode by pressing the Up and Down buttons at the same time. Move to the previous menu screen. Move to the next menu screen. Enter module edit mode to configure the displayed menu value. †...
Menu Items Order Menu Item Range DC module rectifier current Refer to Fig 2.4 Shunt type 50mV 60mV 100mV Max current 0 ~ 999A DC module battery current Refer to Fig 2.5 Shunt type ±50mV 50mV 60mV 100mV Max current 0 ~ 999A DC module digital input channel 1 Refer to Fig 2.6...
Over discharge Over charge DC module digital output channel 1 Refer to Fig 2.10 Digital output channel type Latch Pulse Pulse width time 0.1 ~ 10.0s Fig 2.4 DC module rectifier current shunt Fig 2.5 DC module battery current shunt Fig 2.6 DC module digital input channel 1 of rectifier fault Fig 2.7 DC module digital input channel 2 of rectifier fault Page 50...
Page 51
Fig 2.8 DC module digital input channel 3 of rectifier fault Fig 2.9 DC module digital input channel 4 of rectifier fault Fig 2.10 DC module digital output channel 1 setup Page 51...
APPENDIX A Standard Specification Voltage Input 0 ~ 600V 3 ~ L-L, 0 ~ 457V 3 ~ L-N [Use PTs for voltages over 457V line to line in three phase 3 wire open delta direct] Calibration: 60 ~ 220V per phase ...
APPENDIX B Standard Compliance Accuray IEC62053-22 Class 0.5S Safety UL61010-2, 2 edition[IEC61010] IEC61326-1[IEC61000-4-2]: Electrostatic Discharge[ESD] IEC61326-1[IEC61000-4-3]: EM Field IEC61326-1[IEC61000-4-4]: Electric Fast Transient IEC61326-1[IEC61000-4-5]: Surge Immunity IEC61326-1[IEC61000-4-6]: Conducted RF Immunity IEC61326-1[IEC61000-4-8]: Rated Power Frequency Magnetic Field ...
APPENDIX C Test Report Measuring Test IEC62053-22, Electricity Meter Equipment: active energy for Class 0.5S Current range Power factor Class 0.2S/ 0.5S Accura 3550 0.05A < I < 0.25A ±0.4%/ ±1.0% ±0.4% 0.25A < I < 10.0A ±0.2%/ ±0.5% ±0.2% 0.10A <...
INDEX A M AC Relay, 36 Measurement, 15 Accura PDA, 14 Meter Overview, 20 ANSI 4”, 22 Module Mode, 49 Applications, 17 Mounting, 22 Assembly/Mounting, 19 P B Parameter, 18 Basic Module[DIO Module] Rear Side, 20 Power Quality, 15 Before You Begin, 20 Power Supply, 32, 33, 37 Power Up the Meter, 38 C...
Page 58
Tel. +82+31-695-7350 Fax. +82+31-695-7399 www.rootech.com ⓒ 2006 Rootech Inc. All Rights Reserved Accura EMeter, Accura 2300/2350, Accura 2500, Accura 3300S/3300, Accura 3500S/3500, Accura 3550S/3550, Accura 5500, Accura 7500 are trademarks of Rootech Inc. Contact rootech for detailed specifications and order information.